Plan Review Notes
Plan Review Notes For Project Z18020024
Project Number Z18020024
Review Stop STORM
Sequence Number 3
Notes
Date Text
2018-07-09 16:29:19THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 7/3/18 SUBMITTAL PACKAGE:
  
 1. THE INTENT OF MOVING THE HIGH POINT OF THE DRIVEWAYS
 TOWARD THE PROPERTY LINE IS TO MAXIMIZE THE AMOUNT OF
 RUNOFF DRAINING TO THE ONSITE STORMWATER TREATMENT
 SYSTEM (EXFILTRATION TRENCHES) AS WELL AS LIMIT THE
 VOLUME OF UNCONTROLLED RUNOFF FROM THE SITE. [REFER TO
 PREVIOUS COMMENT NO. 5]
  
 2. THE STORM PIPES ON THE WEST SIDE OF THE BUILDING ARE
 NOT SHOWN ON THE LANDSCAPE PLANS.
  
 3. THERE APPEARS TO BE A CONFLICT BETWEEN PIPE STORM2
 (18? HDPE WITH INVERT ELEVATION 7.00 FT NAVD) AND PIPE
 SAN 5 (6? PVC WITH INVERT ELEVATION BETWEEN 8.02 FEET
 AND 7.61 FEET NAVD).
  
 4. GENERAL NOTE #8 ON SHEET C8 IS IN CONFLICT WITH THE
 DRAINAGE CALCULATIONS AND CALLOUT NOTES IN PLAN VIEW ON
 THE SHEET. REVISE THE GENERAL NOTE TO READ ?? PROVIDE
 78 LF OF 6 FEET WIDE ?? INSTEAD OF ?? PROVIDE 78 LF OF
 4 FEET WIDE ??
  
 5. INDICATE WHERE THE STORMWATER CONTROL STRUCTURE IS
 LOCATED TO CREATE A HYDRAULIC HEAD OF 4.5 FEET (H2)
 (HGL ELEVATION 10.92 FEET NAVD 1988) ASSUMED IN THE
 EXFILTRATION TRENCH CALCULATIONS.
  
 6. DETAIL ST-8 ON SHEET C13 WAS MODIFIED TO SHOW THE
 PIPE SIZE TO BE 12? HDPE. THE STORM STRUCTURE TABLE ON
 SHEET C8 SHOWS THE EXFILTRATION TRENCH PIPE DIAMETER TO
 BE 18? HDPE.
  
 7. SHEET C1 AND THE DRAINAGE SUMMARY REFERS TO AN OLD
 FEMA FIRM AND FLOOD ZONE DESIGNATION. FEMA ISSUED NEW
 FIRMS IN OCTOBER 2017. REFER TO THE SURVEY FOR THE NEW
 PANEL NUMBER.
  
 8. REVISE THE SR# LISTED WITH THE SPEED LIMIT ON SHEET
 C1.
  
 9. PLEASE DATE THE DRAINAGE SUMMARY.
  