2018-03-12 16:15:27FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: CHASE BANK 343 SOUTHERN BLVD Z18020024
 MARCH 12, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. PLEASE PROVIDE A TREE SURVEY AND A TREE DISPOSITION
 LIST IDENTIFYING SPECIES AND TREE CANOPY DIAMETER OF
 TREES AND PALMS, AND INDICATE WHETHER THEY WILL REMAIN,
 BE RELOCATED OR REMOVED. ALL CALCULATIONS AND DATA
 NEEDS TO BE UPDATED WHEN THE LOCATIONS AND SPECIES OF
 ANY TREES TO REMAIN ARE DETERMINED.
 2. PLEASE CORRECT THE REQUIRED OPEN SPACE TO 40 PERCENT
 OF THE TOTAL SITE, AND RECALCULATE REQUIRED TREES AND
 FLOWERING TREES TO CURRENT CODE OF 1 TREE PER 1500 SQ
 FT OF REQUIRED OPEN SPACE OR PRTION THEREOF, AND
 FLOWERING TREES TO ONE PER 6000 SQ FT OR PORTION
 THEREOF.
  
 3. PLEASE PROVIDE THE PERVIOUS LANDSCAPE AREA SQUARE
 FOOTAGE ON THE LANDSCAPE PLAN.
  
 4. PLEASE CORRECT THE BUFFER REQUIREMENTS AND
 CALCULATIONS SHOWN ON THE PLAN. ACCORDING TO THE
 SURVEY, THE EAST AND WEST BUFFER LENGTHS ARE 105 FT,
 AND NORTH AND SOUTH ARE 225 FT. RECALCULATE TREE
 REQUIREMENTS AND SHOW HOW PROVIDED.
  
 5. PLEASE UPDATE FLORIDA FRIENDLY LANDSCAPE POINTS FOR
 THE FOLLOWING ITEMS:
 -CURRENT APPLICABLE CODE REQUIRES 40 POINTS.
 -PROVIDE AN AREA PLAN SHOWING HIGH, MEDIUM AND LOW
 WATER USE ZONES IF POINTS ARE CLAIMED.
  
 6. PALMS SUBSTITUTED FOR REQUIRED BUFFER TREES MUST BE
 AT A 3:1 RATIO FOR EACH TREE.
  
 7. PLEASE PROVIDE A TREE AS REQUIRED IN THE TERMINAL
 LANDSCAPE ISLAND FOR THE ROW OF PARKING ADJACENT TO THE
 DUMPSTER ENCLOSURE.
  
 8. PLEASE EXPLAIN THE REASON FOR THE LONGER THAN 30
 FOOT SPACING FOR THE BUFFER TREES ADJACENT TO THE ATM.
  
 9. PLEASE SHOW LOCATIONS OF ANY FPL TRANSFORMERS ON THE
 LANDSCAPE PLAN.
  
 10. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 11. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED
 EQUIPMENT AND UTILITIES. WATER BACKFLOW VALVES AND FPL
 TRANSFORMERS MUST HAVE SCREENING HEDGES. PLEASE PROVIDE
 LANDSCAPE HEDGE ON THREE SIDES OF DUMPSTER ENCLOSURE AS
 REQUIRED.
  
 12. PLEASE PROVIDE THE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO PREVENT CONFLICTS WITH TREES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  