2018-03-14 12:49:30#1 PROVIDE ESTIMATED FLOWS GPD FOR EACH BUILDING.
  
 #2 BACKFLOW (RPPA AND DCDA) LOCATIONS MUST BE PRE
 APPROVED BY FIRE AND UTILITY CUSTOMER SERVICE FOR EACH
 BUILDING.
  
 #3 PROVIDE TIMELINE AS TO WATERMAIN UPGRADE TO 12" WM.
  
 #4 PROVIDE PRELIMINARY SUMMARY AS TO THE EXISTING SEWER
 CAPACITY WITH CITY OF WPB PUBLIC UTILTIES.
  