| 2018-03-13 10:26:03 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 |
| | PROJECT: 1125 OKEECHOBEE RD. Z18020018 |
| | MARCH 12, 2018 |
| | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND |
| | PROVIDE THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1. PLEASE SHOW LOCATIONS OF ADJACENT BUILDINGS, HEDGES |
| | AND TREES ON THE LANDSCAPE PLAN. |
| | |
| | 2. PLEASE SHOW AND LABEL THE REQUIRED 5 FOOT LANDSCAPE |
| | BUFFER ON SIDES AND REAR PROPERTY LINES, AND 10 FOOT |
| | LANDSCAPE BUFFER ADJACENT TO THE STREET. |
| | |
| | 3. SHOW CALCULATIONS TO MEET REQUIRED TREE COUNT FOR |
| | EACH BUFFER LENGTH. |
| | |
| | 4. PLEASE SHOW COMPLIANCE WITH THE 20 PERCENT BUILDING |
| | PERIMETER LANDSCAPING REQUIREMENT. |
| | |
| | 5. THE CIVIL ENGINEERING PLAN SUBMITTED SHOWS LANDSCAPE |
| | SYMBOLS, PROPOSED LANDSCAPING SHOULD ONLY BE SHOWN ON |
| | THE LANDSCAPE PLAN. |
| | |
| | 6. PLEASE CORRECT THE REQUIRED OPEN SPACE TO 40 PERCENT |
| | OF THE TOTAL SITE, AND RECALCULATE REQUIRED TREES AND |
| | FLOWERING TREES. |
| | |
| | 7. PROVIDE CURBS FOR ALL VEHICULAR USE AREAS ADJACENT |
| | TO LANDSCAPING. |
| | |
| | 8. PLEASE PROVIDE THE BUFFER REQUIREMENTS AND |
| | CALCULATIONS ON THE PLAN. |
| | |
| | 9. PLEASE UPDATE FLORIDA FRIENDLY LANDSCAPE POINTS FOR |
| | THE FOLLOWING ITEMS: |
| | - APPLICABLE CODE REQUIRES 40 POINTS. |
| | -PROVIDE AN AREA PLAN SHOWING HIGH, MEDIUM AND LOW |
| | WATER USE ZONES IF POINTS ARE CLAIMED. |
| | -PROVIDE INFORMATION ON MOISTURE SENSOR OR EFFICIENT |
| | CONTROLLER IF POINTS ARE CLAIMED. |
| | |
| | 10. PLEASE ADD A COLUMN FOR DROUGHT TOLERANCE TO THE |
| | PLANT LIST AND PROVIDE THE LEVEL FOR EACH SPECIES. |
| | |
| | 11. PLEASE PROVIDE A TREE AS REQUIRED IN THE TERMINAL |
| | LANDSCAPE ISLAND ON BOTH SIDES OF PARKING SPACES. |
| | |
| | 12. PLEASE SHOW LOCATIONS OF ANY FPL TRANSFORMERS ON |
| | THE LANDSCAPE PLAN. |
| | |
| | 13. PLEASE SHOW ALL WATER, SEWAGE AND DRAINAGE LINES ON |
| | THE LANDSCAPE PLAN. |
| | |
| | 14. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT |
| | INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES |
| | WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY |
| | FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS. |
| | |
| | 15. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED |
| | EQUIPMENT AND UTILITIES. WATER BACKFLOW VALVES AND FPL |
| | TRANSFORMERS MUST HAVE SCREENING HEDGES. PLEASE PROVIDE |
| | LANDSCAPE HEDGE ON THREE SIDES OF DUMPSTER ENCLOSURE AS |
| | REQUIRED. |
| | |
| | 16. PLEASE PROVIDE THE LOCATIONS OF LIGHTING ON THE |
| | LANDSCAPE PLAN TO PREVENT CONFLICTS WITH TREES. |
| | |
| | CONDITIONS OF APPROVAL |
| | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON |
| | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE |
| | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT |
| | SERVICES DEPARTMENT, PLANNING DIVISION. |
| | |
| |