Plan Review Notes
Plan Review Notes For Project Z18010013
Project Number Z18010013
Review Stop STORM
Sequence Number 3
Notes
Date Text
2018-06-01 16:51:26A REVIEW WAS MADE OF THE MAY 29, 2018 SUBMITTAL
 PACKAGE. THE STATUS OF THE COMMENTS ARE FROM THE REVIEW
 OF THE APRIL 12, 2018 SUBMITTAL PACKAGE ARE AS FOLLOWS:
  
 1. VERTICAL DATUM ON THE SURVEY AND ENGINEERING PLANS
 NEEDS TO BE CONSISTANT. ELEVATIONS ON THE SURVEY ARE
 INDICATED TO BE IN REFERENCE TO NAVD 1988. ELEVATIONS
 ON THE ENGINEERING PLANS ARE INDICATED TO BE IN
 REFERENCE TO NGVD 1929. EXISTING SPOT GRADE VALUES ARE
 THE SAME ON THE SURVEY AND ENGINEERING PLANS. COMMENT
 SATISFIED. BOTH PLANS ARE USING NAVD1988 AS THE
 VERTICAL DATUM.
  
 2. THE CONVERSION (DIFFERENCE) BETWEEN NAVD 1988 AND
 NGVD 1929 VERTICAL DATUMS LISTED ON THE SURVEY AND ON
 THE ENGINEERING PLANS NEEDS TO BE CONSISTANT. ONE USES
 1.52 FEET AND THE OTHER USES 1.53 FEET. COMMENT
 SATISFIED. BOTH PLANS ARE USING THE 1.53 FEET
 CONVERSION FACTOR BETWEEN NAVD AND NGVD.
  
 3. SHEET C4.00 LISTS THE FINISHED FLOOR ELEVATION AS
 12.00 FEET NGVD. SHEET A1.0 LISTS THE FINISHED FLOOR
 ELEVATION AS 12 FT 6 INCHES.NGVD. COMMENT NOT ADDRESSED
 OTHER THAN CHANGING THE VERTICAL DATUM ON SHEET C4.00.
 THE FINISHED FLOOR IS LISTED AS 12.00 FEET NAVD. SHEET
 A1.0 STILL LISTS THE FINISHED FLOOR ELEVATION AS 12 FT
 6 INCHES NGVD.
  
 4. SHEET C4.00 SHOWS ONSITE CONCRETE STEPS ALONG THE
 NORTH SIDE OF THE ALLEY ACROSS THE DRIVEWAY TO THE
 TRASH / GAS '/ GENERATOR ROOM AND OUTSIDE THE DOOR TO
 THE STAIRWELL AT THE EAST END OF THE ALLEY. NEITHER
 SETS OF STEPS ARE SHOWN ON THE SITE PLAN (SHEET A1.0).
 INDICATE HOW THE TRASH BE HANDLED IF THERE ARE STEPS IN
 THIS LOCATION. CAN THE BOTTOM FLOOR OF THE STAIRWELL BE
 TAKEN DOWN TO THE ELEVATION OF THE ALLEY SO STEPS WILL
 NOT BE NEEDED OUTSIDE THE DOOR? COMMENT SATISFIED. THE
 STEPS IN FRONT OF THE TRASH ROOM HAVE BEEN ELIMINATED.
 THE STEPS AT THE EAST END OF THE ALLEY HAVE BEEN TURNED
 90 DEGREES.
  
 5. PROVIDE DETAIL OF THE EXFILTRATION TRENCH INCLUDING
 WIDTH AND TOP ELEVATION OF THE TRENCH. COMMENT
 SATISFIED. SHEET C4.00 LABELS THE TRENCH AS 4 FEET WIDE
 BY 4 FEET HIGH.
  
 6. PROVIDE THE WEIR ELEVATION FOR STRUCTURE ST-01.
  
 7. MINIMUM 15" RCP STORM PIPE WITHIN THE PUBLIC
 RIGHT-OF-WAY.
  
 ADDITIONAL COMMENTS FROM THE MAY 29, 2018 SUBMITTAL
 PACKAGE:
 8. LABEL THE DRAINAGE FIXTURES ACROSS THE DRIVEWAYS AS
 "TRENCH" DRAINS AND NOT "FRENCH" DRAINS.
  
 9. ADD'L COMMENTS TO BE ADDED.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  
  
  
  
  