2018-02-12 12:07:25CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 DATE: 02/12/2018
 PROJECT: GOOD SAMARITAN MOB
 ADDRESS: 300 PALM BEACH LAKES BLVD
 STATUS: FAILED
  
 THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. FOLLOWING COMMENTS NEED TO BE
 ADDRESSED PRIOR TO SITE PLAN APPROVAL:
  
 1. ADVISORY: BURGER KING IS CURRENTLY GOING THROUGH THE
 BUILDING SERVICES DEPARTMENT AND ARE PROPOSING TO
 REMOVE THE 12-INCH RCP;
  
 2. SIDEWALK SHOULD CONTINUE ALONG THE RIGHT-OF-WAY LINE
 OF PALM BEACH LAKES AND SHALL NOT BE DEFLECTED ONSITE.
 DEVIATED SIDEWALK IS TO BE CONSIDERED AS PRIVATE;
  
 3. DRIVEWAY APRONS SHALL COMPLY WITH CITY STANDARD
 DETAIL GC-6: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUB
 LIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 4. DETECTABLE WARNING SURFACES MARK BOUNDARIES BETWEEN
 PEDESTRIAN AND VEHICULAR WAYS WHERE THERE IS NO RAISED
 CURB SUCH AS RAMPS WILL BE REQUIRED. DETECTABLE WARNING
 SURFACES ARE REQUIRED BY 49 CFR, PART 37 AND BY THE
 AMERICANS WITH DISABILITIES ACT (ADA) WHERE CURB RAMPS
 ARE CONSTRUCTED AT THE JUNCTION OF SIDEWALKS AND THE
 ROADWAY, FOR MARKED AND UNMARKED CROSSWALKS. DETECTABLE
 WARNING SURFACES CONTRAST VISUALLY WITH ADJACENT
 WALKING SURFACES, EITHER LIGHT-ON-DARK, OR
 DARK-ON-LIGHT. THE AMERICANS WITH DISABILITIES ACT
 ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES
 (ADAAG).
  
 5. INCLUDE CROSSWALK MARKINGS WHICH PROVIDE GUIDANCE
 FOR PEDESTRIANS WHO ARE CROSSING DRIVEWAYS BY DEFINING
 AND DELINEATING PATHS ON APPROACHES.
  
 6. PUBLIC UTILITIES DEPARTMENT NEEDS TO ASSESS EXISTING
 LIFT STATION CONDITIONS;
  
 7. SANITARY SEWER SHOULD CONNECT FROM N. OLIVE AVENUE
 AND NOT FROM THE ALLEYWAY;
  
 8. PHOTOMETRIC ANALYSIS WAS NOT PROVIDED FOR DRIVEWAY
 CONNECTING TO ALLEYWAY;
  
 9. SUBMIT ESTIMATES FOR WATER AND FIRE DEMAND, BOTH
 AVERAGE AND PEAK FLOW WITH PEAKING FACTOR. ALSO SUBMIT
 ESTIMATES OF SANITARY SEWER FLOW FOR THE PROPOSED
 DEVELOPMENT. SHOW PROJECTED DEMANDS ON THE UTILITY PLAN
 SHEET;
  
 10. THE AVAILABLE WATER PRESSURE IN THIS PORTION OF THE
 CITY MAY NOT BE ACCEPTABLE AT ELEVATIONS HIGHER THAN
 THE 2ND FLOOR. WE RECOMMEND A LONG-TERM PRESSURE STUDY
 BE PERFORMED PRIOR TO FINALIZATION OF THE UTILITY
 DESIGN;
  
 11. A MAINTENANCE AGREEMENT WILL BE REQUIRED FOR THE
 NON-STANDARD ELEMENTS (TREES AND TREE GRATES; PAVERS,
 ETC.) PROPOSED WITHIN RIGHT-OF-WAYS;
  
 AFTER THE SITE PLAN IS APPROVED, IN THE NEXT PHASE, THE
 FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL:
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK: HTTP
 ://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-
 PERMITS-APPLICATIONS
  
 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC
 CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL
 WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE
 FOLLOWING LINK:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 3. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND
 SANITARY SEWER CALCULATION (IN DETAIL I.E. AVERAGE AND
 PEAK WITH PEAKING FACTOR). SUBMIT CALCULATIONS TO
 VALIDATE METER SIZE SELECTION. SHOW THESE CALCULATIONS
 ON THE UTILITY PLAN SHEET AS WELL;
  
 4. CCTV MUST BE PROVIDED FROM MANHOLE TO MANHOLE WHERE
 THE PROPOSED SANITARY SEWER WILL BE LOCATED. CONTACT ME
 FOR THE MANHOLE NUMBER AND SUBMIT CD WITH THE
 ENGINEERING DEVELOPMENT APPROVAL APPLICATION.
 COORDINATE WITH UTILITIES O&M SANITARY SEWER
 SUPERINTENDENT CHARLES PHOENIX PROVIDE 48-HOUR NOTICE
 AND MUST OBTAIN A RIGHT-OF-WAY PERMIT;
  
 5. SHOW THE NEAREST FIRE HYDRANT TO THIS SITE ON THE
 FINAL UTILITY PLAN. FIRE HYDRANT FLOW TEST DATA FROM
 EXISTING FIRE HYDRANT WILL BE REQUIRED PART OF THE PLAN
 SUBMITTAL. SHOW HYDRANT FLOW TEST DATA RESULT ON THE
 PLANS;
  
 6. FIRE HYDRANT TEST CAN BE REQUESTED AT (561)804-4700;
  
 7. ALL PROPOSED FIRE DEPARTMENT CONNECTIONS SHALL BE
 WITHIN 100 FEET OF A FIRE HYDRANT AND SHALL BE WITHIN
 AN EASEMENT WITHIN THE PROPERTY;
  
 8. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE
 CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE
 DETAIL SHEET/S DURING SUBMISSION OF THE FINAL
 ENGINEERING PLANS. CONTACT THE ENGINEERING SERVICES
 DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD
 FORMAT. CITY'S STANDARD DETAILS (IN PDF FILE FORMAT)
 CAN BE DOWNLOADED FROM THE FOLLOWING SITE: HTTP://WPB.O
 RG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS-
 APPLICATIONS
  
 9. PLACEMENT OF THE ANY PROPOSED METER, BACKFLOW
 PREVENTER, DCDA ETC. SHALL BE INSTALLED PER THE CITY?S
 STANDARD DETAILS. WATER METER SHOULD BE WITHIN THE
 RIGHT-OF-WAY OR INSIDE AN 'UTILITY EASEMENT' JUST
 INSIDE THE PROPERTY NEAR THE RIGHT-OF-WAY AND
 ACCESSIBLE;
  
 10. IN THE FINAL PLANS, MUST PROVIDE UTILITY CONFLICT
 TABLE (BOTTOM AND TOP OF CROSSING PIPES) AT THE
 CONFLICT POINTS OF ALL WATER, STORM AND SANITARY SEWER
 PIPES AS WELL AS OTHER FRANCHISE UTILITIES. EXISTING
 UTILITIES WITHIN THE PROPOSED SANITARY SEWER LATERAL
 ARE TO BE VERIFIED VIA SOFTDIGS, PROVIDE ALL UTILITY
 CROSSING INFORMATION;
  
 11. IN THE FINAL PLANS, SHOW DIRECTION OF FLOW FOR THE
 EXISTING SANITARY SEWER. SHOW INVERT AT CONNECTION
 POINTS AND INCLUDE A PROFILE FOR THE PROPOSED SERVICE
 LATERAL WITH GROUND ELEVATIONS ABOVE THE PIPE;
  
 12. PAVEMENT RESTORATION FOR OPEN CUT/TRENCH FOR
 UTILITY CONNECTION WORKS WILL NEED TO BE IN ACCORDANCE
 WITH 2016 CITY STANDARD DETAIL GC-9. THE ROAD SHALL BE
 MILLED/RESURFACED FOR FULL LANE WIDTH OF THE TRAVEL
 LANE(S) ENCROACHED BY THE TRENCH AREA, INCLUDING A
 TRANSITION AREA OF 50 FEET ON EACH SIDE OF THE TRENCH.
 PLEASE SHOW ON THE FINAL PLANS THE EXTENT OF THE
 MILLING AND RESURFACING;
  
 13. SHOW ON THE FINAL PLANS SIZE AND MATERIAL OF ALL
 EXISTING UTILITIES ON PALM BEACH LAKES BLVD, N. OLIVE
 AVE AND ALLEYWAY INCLUDING BUT NOT LIMITED TO WATER,
 SEWER, GAS, UNDERGROUND ELECTRIC CONDUITS ETC. PLEASE
 IDENTIFY THE SOURCE OF THE AS-BUILT INFORMATION
 UTILIZED FOR THE POTABLE WATER, SANITARY SEWER, AND
 STORM SEWER DESIGN;
  
 14. FOR THE FINAL WATER AND SEWER PLANS, INCLUDE A NOTE
 THAT: AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM
 BEACH CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW: HT
 TP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICA
 TIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved