Plan Review Notes
Plan Review Notes For Project Z18010013
Project Number Z18010013
Review Stop B
Sequence Number 1
Notes
Date Text
2018-02-13 18:08:34DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. ACCESSIBLE PARKING. SHEET A1.0, SITE PLAN, SHOWS
 THAT 142 PARKING SPACES WILL BE PROVIDED SO 5
 ACCESSIBLE PARKING SPACES ARE REQUIRED. THE SUBMITTED
 PLANS DO NOT SHOW 5 ACCESSIBLE PARKING SPACES AND ONLY
 SHOW 1 ACCESSIBLE PARKING SPACE ON THE MAIN ENTRY
 LEVEL. THE MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES
 PROVIDED SHALL BE IN ACCORDANCE WITH SECTION 208.2 OF
 FLORIDA ACCESSIBILITY CODE.
  
 3. VAN ACCESSIBLE PARKING. THE PLANS DO NOT CALL OUT
 THE LOCATION OF A VAN ACCESSIBLE PARKING SPACE. PER
 SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE IN
 EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING
 STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN
 ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY
 CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT
 SPACE AND VEHICULAR ACCESS ROUTE)
  
 4. LOCATION OF ACEESIBLE PARKING. CANNOT DETERMINE
 WHETHER THE ACCESSIBLE PARKING SPACES ARE CORRECTLY
 LOCATED BECAUSE SHEETS A2.1 AND A2.2, LEVEL 2 AND LEVEL
 3 - OVERALL PLAN, DO NOT CLEARLY SHOW THE ENTRANCE TO
 THE BUILDING FROM THE PARKING GARAGE OR THE ROUTE TO
 THE ELEVATOR. PER SECTION 208.3 OF FLORIDA
 ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES ARE TO BE
 LOCATED ON THE SHORTEST POSSIBLE ROUTE OF TRAVEL FROM
 ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE FOR EACH
 BUILDING.
  
 5. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 6. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 7. IS THIS AN ENCLOSED PARKING GARAGE OR AN OPEN
 PARKING GARAGE? IF THE PARKING GARAGE DOES NOT HAVE
 WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO MEET THE
 DEFINITION OF AN OPEN PARKING GARAGE, IT WILL BE
 CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 8. LEVEL 2 EGRESS FROM PARKING GARAGE. SHEET A2.1,
 LEVEL 2 - OVERALL PLAN, DOES NOT SHOW A ROUTE FOR
 OCCUPANTS ON LEVEL 2 OF THE PARKING GARAGE TO GET TO
 THE EAST STAIR.
  
 9. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 10. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC
 PLACES (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION
 OF PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT,
 CONTACT SYBILLE WELTER, ART IN PUBLIC PLACES
 COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  