| 2018-01-31 15:07:17 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. THE BUILDING ADDRESSES SHALL BE CLEARLY VISIBLE FROM |
| | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. |
| | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND |
| | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT |
| | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE |
| | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE |
| | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH |
| | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, |
| | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. |
| | |
| | FOR INFORMATIONAL AND PLAN SUBMITTAL PURPOSES, THE |
| | PARKING GARAGES, STAND ALONE AND UNDER THE RESIDENTIAL |
| | APARTMENTS, QUALIFIES AS ENCLOSED PARKING STRUCTURE AND |
| | WOULD FALL UNDER NFPA 88A FOR LIFE SAFETY CODE |
| | REQUIREMENTS. |
| | |
| | |
| | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE |
| | OCCUPANCY TYPE OR EACH STRUCTURE, PER THE FLORIDA FIRE |
| | PREVENTION CODE, AND WHETHER IT IS MIXED OR SEPARATED |
| | OCCUPANCY, WHERE APPLICABLE. |
| | |
| | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE |
| | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER |
| | SUPPLY IS EXISTING OR WILL BE PROVIDED. |
| | |
| | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| | ON THE PLAN. |
| | |
| | THE LOCATIONS PROPOSED DO NOT TO PROVIDE FOR THE |
| | OPTIMAL FIRE OPERATIONS USE AND CONTROL. |
| | |
| | THE BUREAU OF FIRE PREVENTION WOULD LIKE THE |
| | OPPORTUNITY TO REVIEW AND COORDINATE THE LOCATIONS OF |
| | THE FIRE HYDRANTS AND FDC?S PLANNED FOR THIS |
| | DEVELOPMENT. |
| | |
| | IT IS OFTEN BEST FOR THE FIRE HYDRANTS AND FDC?S TO BE |
| | LOCATED ON THE SAME SIDE OF THE STREET OR ACCESS |
| | ROADWAY TO ALLOW FREE ACCESS FOR OTHER ARRIVING |
| | EMERGENCY VEHICLES. |
| | |
| | THE BUREAU LOOKS FORWARD TO MEETING AND DISCUSSING |
| | VARIOUS LOCATION OPTIONS IN THE FUTURE. |
| | |
| | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER |
| | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY |
| | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, |
| | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND |
| | SUBMITTED WITH THE MASTER PLAN. |
| | |
| | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL |
| | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, |
| | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A |
| | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE |
| | SAFETY FEATURES AND EQUIPMENT. |
| | |
| | 11. IT IS HIGHLY RECOMMENDED FOR ANY ACCESS GATES THAT |
| | THEY BE PROVIDED WITH KNOX KEY ACCESS LOCKS, PADLOCKS |
| | AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. |
| | |
| | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT |
| | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| | |
| | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| |