2018-03-29 09:02:48THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE PLANS
 IN THE 3/12/2018 ROUTED REVIEW PACKAGE. THEY CAN BE
 MADE A CONDITION OF SITE PLAN APPROVAL.
  
 1. THE CONVERSION EQUATION BETWEEN NAVD 1988 AND NGVD
 1929 NEED TO BE CONSISTENT ON THE SURVEY AND
 ENGINEERING PLANS. THE SURVEY USES 1.53' AND THE
 ENGINEERING PLANS USE 1.52'.
  
 2. REDUCE THE SIDEWALK APPROACH ON THE NORTH SIDE OF
 THE CURB RAMP AT THE INTERSECTION OF ELIZABETH ST AND
 WILKINS AVE. TRY TO KEEP THE APPROACH WITHIN THE CROSS
 WALK STRIPING.
  
 3. STRUCTURE S-301 APPEARS TO BE A CONTROL STRUCTURE
 FOR THE ONSITE DRAINAGE SYSTEM. THE CONTROL STRUCTURE
 NEEDS TO BE ONSITE.
  
 4. PROPOSED FIRE HYDRANT #1 AT CLARE AVE AND WILKINS
 AVE NEEDS TO BE WITHIN THE RIGHT-OF-WAY OR IN A UTILITY
 EASEMENT.
  
 5. THE WATER MAIN TO PROPOSED FH #2 APPEARS TO ME IN
 CONFLICT WITH STRUCTURE S-304.
  
 6. SEPARATE ENGINEERING PLANS WILL NEED TO BE PROVIDED
 FOR OFFSITE WORK.
  
 7. THE CITY'S TRANSPORTATION GROUP TO REVIEW/APPROVE
 THE MID-BLOCK CROSSWALK ON BLANCHE ST.
  
 8. THE ONSITE DRAINAGE SYSTEM TO MEET SFWMD CRITERIA
 FOR WATER QUALITY AND PRE- VS. POST-DEVELOPMENT OFFSITE
 DISCHARGE RATE.
  
 9. THE EXISTING STORM MANHOLE IN THE INTERSECTION OF
 CLARE AVE AND BLANCH ST MAY NEED TO BE REPLACED/UPSIZED
 TO RECEIVE NEW 36" RCP FROM WEST AND 24" RCP FROM
 SOUTHWEST.
  
 10. ADD NEW PIPE LINE SYMBOL FOR 24" RCP FROM STRUCTURE
 S-304 TO EXISTING MANHOLE IN INTERSECTION OF CLARE AVE
 AND BLANCHE ST.
  