Plan Review Notes
Plan Review Notes For Project Z17120025
Project Number Z17120025
Review Stop B
Sequence Number 2
Notes
Date Text
2018-05-22 11:10:09DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. RESPONSE LETTER DATED 3/1/18 IS NOTED AND ADDRESSES
 THE FOLLOWING COMMENT - ACCORDING TO THE ADOPTED FLOOD
 INSURANCE RATE MAPS (FIRMS), THE PROPOSED BUILDING IS
 IN A FLOOD ZONE. THE FIRST FLOOR OF THE BUILDING AND
 ALL ASSOCIATED MECHANICAL EQUIPMENT (CHILLERS,
 GENERATORS ETC.) SHALL BE 24 INCHES (FREEBOARD) ABOVE
 THE BASE FLOOD ELEVATION.
  
 3. RESPONSE LETTER DATED 3/1/18 IS NOTED AND ADDRESSES
 THE COMMENT REGARDING ACCESSIBLE PARKING.
  
 4. WHEN SUBMITTED FOR PERMIT THE PLANS SHALL BE MARKED
 TO SHOW WHICH ACCESSIBLE PARKING SPACES ARE DESIGNATED
 AS VAN ACCESSIBLE. RESPONSE LETTER DATED 3/1/18 IS
 NOTED AND PARTIALLY ADDRESSES THE COMMENT REGARDING VAN
 ACCESSIBLE PARKING.
  
 5. RESPONSE LETTER DATED 3/1/18 IS NOTED AND ADDRESSES
 THE FOLLOWING COMMENT - BUILDING SIZE. WHEN SUBMITTED
 FOR BUILDING PERMIT, THE PLANS SHALL SHOW THAT THE TYPE
 OF CONSTRUCTION FOR THE BUILDINGS WILL BE IN ACCORDANCE
 WITH THE HEIGHT, AREA AND OCCUPANCY LIMITATIONS IN
 CHAPTER 5 OF THE FLORIDA BUILDING CODE.
  
 6. RESPONSE LETTER DATED 3/1/18 IS NOTED AND ADDRESSES
 THE FOLLOWING COMMENT - BUILDING LOCATION RELATIVE TO
 THE PROPERTY LINE AND OTHER STRUCTURES. WHEN SUBMITTED
 FOR BUILDING PERMIT, COMPLIANCE WITH ALL BUILDING
 SEPARATION, PERCENTAGE OF OPENINGS AND OPENING
 PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF THE
 FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 7. RESPONSE LETTER DATED 3/1/18 IS NOTED AND ADDRESSES
 THE COMMENT REGARDING SOUND ATTENUATION FOR THE
 MECHANICAL VENTILATION OF THE PARKING GARAGE.
  
 8. RESPONSE LETTER DATED 3/1/18 IS NOTED AND ADDRESSES
 THE COMMENT REGARDING MEANS OF EGRESS FROM THE
 RESIDENTIAL UNITS.
  
 9. RESPONSE LETTER DATED 3/1/18 IS NOTED AND ADDRESSES
 THE FOLLOWING COMMENT - GREASE INTERCEPTOR. A GREASE
 INTERCEPTOR WILL BE REQUIRED. PLEASE CONTACT JEFFREY
 ODOMS, UTILITIES O&M SUPERINTENDENT, PUBLIC UTILITIES
 DEPARTMENT, FATS OILS AND GREASE DIVISION, AT (561)
 822-2172, OR BY EMAIL: [email protected]
  
 10. RESPONSE LETTER DATED 3/1/18 IS NOTED AND ADDRESSES
 THE FOLLOWING COMMENT - SEPARATE PERMITS REQUIRED. ALL
 APPLICABLE PERMITS AND SUB-PERMITS MUST BE OBTAINED
 BEFORE COMMENCING THE WORK. SEPARATE PERMITS, PLANS AND
 FEES, ARE REQUIRED FOR SIGNS, SWIMMING POOLS AND SPAS,
 GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, FIRE
 SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, GREASE
 INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, SITE
 IRRIGATION, ETC.
  
 11. RESPONSE LETTER DATED 3/1/18 IS NOTED AND ADDRESSES
 THE FOLLOWING COMMENT - EACH SEPARATE BUILDING SHALL
 HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494
 1080, OR BY EMAIL: [email protected]
  
 12. RESPONSE LETTER DATED 3/1/18 IS NOTED AND ADDRESSES
 THE FOLLOWING COMMENT - THIS PROJECT WILL BE SUBJECT TO
 ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE ON
 THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  