2018-06-04 08:23:08THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE JUNE
 1, 2018 SUBMITTAL REVIEW PACKAGE:
  
 1. ON SHEET E-1, LABEL THE RETENTION AREAS AS DETENTION
 AREAS UNLESS IT IS DETERMINED THERE IS NOT AN OUTFALL
 FOR THE AREA(S).
  
 2. SINCE THE PROPERTY IS BEING RE-PLATTED AND
 RE-DEVELOPED AND THE EXISTING DRAINAGE SYSTEM
 (DETENTION PONDS) WILL CONTINUE TO SERVE THE OVERALL
 DEVELOPMENT, THE EXISTING DRAINAGE SYSTEM SHOULD BE
 CHECKED TO SEE IF IT IS SUFFICIENTLY SIZED FOR THE
 CHANGE IN DEVELOPMENT CRITERIA (IMPERVIOUS/PERVIOUS
 AREAS, BUILDING FOOT PRINT AREAS, ETC.). THE EXISTING
 DETENTION PONDS MAY NEED TO BE ENLARGED WHICH MAY
 AFFECT THEIR PLATTED PARCEL BOUNDARIES.
  