| 2017-12-11 19:21:53 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. |
| | |
| | 2. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND |
| | POTENTIAL SPREAD OF FIRE TO OTHER (FUTURE) STRUCTURES. |
| | DUE TO THE PROXIMITY OF THE NORTH-WEST WALL OF THE |
| | EXISTING BUILDING TO THE PROPOSED PROPERTY LINE BETWEEN |
| | PARCEL NO. 1 AND PARCEL NO. 5A, COMPLIANCE WITH ALL |
| | BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND OPENING |
| | PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF THE |
| | FLORIDA BUILDING CODE MUST BE VERIFIED. COMPLIANCE WITH |
| | TABLE 705.8 OF THE FLORIDA BUILDING CODE MUST BE |
| | DEMONSTRATED. THEREFORE PLANS MUST BE SUBMITTED TO SHOW |
| | THE FIRE RESISTACE RATING OF THE NORTH-WEST WALL AND |
| | THE PERCENTAGE OF THAT WALL THAT IS TAKEN UP BY DOOR |
| | AND WINDOW OPENINGS WHICH ARE NOT FIRE-RESISTANCE |
| | RATED. THE SAME APPLIES TO THE CENTER PORTION OF THE |
| | NORTH-EAST WALL WHICH FACES PROPOSED PARCEL NO. 3. |
| | |
| | 3. EXITS ON THE NORTH-WEST ELEVATION. A FLOOR PLAN, |
| | LIFE SAFETY PLAN OR OTHER FORM OF PLAN SHALL BE |
| | SUBMITTED TO SHOW THAT THERE IS NO REQUIRED EXIT |
| | REQUIREMENT ON THE NORTH-WEST ELEVATION. ANY EXIT MAY |
| | NOT DISCHARGE ONTO A DIFFERENT PROPERTY, SO IT MUST |
| | DISCHARGE EITHER ONTO THE SAME PROPERTY AS THE BUILDING |
| | WHICH IT SERVES OR IT MUST DISCHARGE ONTO THE |
| | RIGHT-OF-WAY. THE PROPOSED PROPERTY LINE BETWEEN PARCEL |
| | NO. 1 AND PARCEL NO. 5A APPEARS TO BE ON THE NORTH-WEST |
| | WALL OF THE EXISTING BUILDING, SO ANY EXIT THROUGH THAT |
| | WALL WOULD BE DISCHARGING ONTO A DIFFERENT PROPERTY. |
| | THE SAME APPLIES TO THE CENTER PORTION OF THE |
| | NORTH-EAST WALL WHICH FACES PROPOSED PARCEL NO. 3. |
| | |
| | 4. THE PROPOSED PROPERTY LINE BETWEEN PARCEL NO. 1 AND |
| | PARCEL NO. 5A APPEARS TO BE ON THE NORTH-WEST WALL OF |
| | THE EXISTING BUILDING. THERE IS NOT SUFFICIENT DETAIL |
| | TO CLEARLY SHOW THAT THE EXISTING BUILDING WILL NOT |
| | CROSS THAT PROPOSED PROPERTY LINE. FOR ANY BUILDING |
| | CROSSING A PROPERTY LINE, EITHER A RECORDED UNITY OF |
| | TITLE, OR SOME OTHER APPROVED LEGAL INSTRUMENT, SHALL |
| | BE SUBMITTED, OR THE BUILDING MUST HAVE A FIRE WALL |
| | ALONG THE PROPERTY LINE, PER SECTION 202 OF FLORIDA |
| | BUILDING CODE, BUILDING, FIRE SEPARATION DISTANCE. THE |
| | SAME APPLIES TO THE CENTER PORTION OF THE NORTH-EAST |
| | WALL WHICH FACES PROPOSED PARCEL NO. 3. |
| | |
| | 5. EACH SEPARATE BUILDING WILL NEED A SEPARATE ADDRESS. |
| | FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, GIS |
| | SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: |
| | [email protected] |
| | |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |