2018-01-08 11:28:55THE FOLLOWING COMMENTS NEED TO BE ADDRESSED PRIOR TO
 APPROVAL OF SITE PLAN:
 1 - A 4' HIGH ROLLING GATE IS SHOWN AT BOTH DRIVEWAYS
 ON DATURA STREET. THE PROPOSED LOCATION OF THE GATE
 WILL CAUSE CARS TO BLOCK THE SIDEWALK WHILE UTILIZING
 THE GATE. QUEUING CAN'T OCCUR IN RIGHT OF WAY.
 SEC. 78-1. - OBSTRUCTING PASSAGE ON STREETS, SIDEWALKS
 AND BICYCLE PATHS PROHIBITED.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO OBSTRUCT OR
 HINDER THE FREE FLOW OF PEDESTRIAN OR VEHICULAR TRAFFIC
 ON ANY STREET, SIDEWALK OR BICYCLE PATH IN THE CITY.
 SEC. 94-111. - PARKING AND LOADING REQUIREMENTS (P)
 QUEUING. NOT LESS THAT 20 LINEAR FEET SHALL BE PROVIDED
 FOR CAR QUEING, SHALL OCCUR INTERNAL TO THE LOT, AND
 SHALL NOT INTERFERE WITH PEDESTRIAN CIRCULATION ON A
 PUBLIC SIDEWALK.
  
 2 - THERE ARE TWO DRIVEWAYS SHOWN ON DATURA STREET. THE
 MAXIMUM NUMBER OF ACCESS POINTS (DRIVEWAYS) IS ONE.
 REFERENCE SEC. 94-312. - ACCESS TO STREETS. APPLICANT'S
 RESPONSE TO PREVIOUS COMMENTS STATES THAT EXISTING
 DRIVEWAYS ARE GRANDFATHERED. PROVIDE CODE OF ORDINANCES
 REFERENCE THAT ALLOWS DRIVEWAY TO BE GRANDFATHERED.
  
 ERIK D. FERGUSON, P.E.
 CITY TRANSPORTATION ENGINEER