2017-12-27 11:45:36CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 DATE: 12/27/2017
 PROJECT: 302 DATURA STREET REMODELING
 ADDRESS: 302 DATURA STREET
 STATUS: FAILED
  
 THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND POLLUTION PREVENTION
 PLAN WILL BE REVIEWED AS PART OF THE ENGINEERING
 DEVELOPMENT APPROVAL AND BUILDING PERMIT APPLICATION
 PROCESSES. FOLLOWING COMMENTS NEED TO BE ADDRESSED
 PRIOR TO SITE PLAN APPROVAL:
  
 1. PLEASE SHOW ON THE PLANS, HOW WILL THE SITE/BUILDING
 BE SERVED FOR WATER, SEWER AND FIRE PROTECTION. SHOW
 ALL EXISTING UTILITIES WITHIN THE VICINITY OF THE
 PROPOSED SITE AS WELL AS PROPOSED UTILITIES TO SERVE
 THE DEVELOPMENT (LABEL SIZE AND MATERIAL OF ALL PIPES
 AND CONDUITS ETC.);
  
 2. SUBMIT ESTIMATES FOR WATER AND FIRE DEMAND, BOTH
 AVERAGE AND PEAK FLOW WITH PEAKING FACTOR. ALSO SUBMIT
 ESTIMATES OF SANITARY SEWER FLOW FOR THE PROPOSED
 DEVELOPMENT. SHOW PROJECTED DEMANDS ON THE UTILITY PLAN
 SHEET;
  
 3. ON THE LANDSCAPING PLAN, WHEN SUBMITTED IN THE NEXT
 REVIEW PHASE, SHOW LOCATIONS OF ALL WATER METERS,
 VALVES, CLEAN-OUTS, LIGHT POLES, ETC. ROOT BARRIERS MAY
 BE REQUIRED WHERE PLANTINGS ARE NEAR UNDERGROUND
 STORMWATER, SANITARY, OR POTABLE WATER LINES. ALSO
 CLEARLY INDICATE ALL EXISTING AND PROPOSED EASEMENTS ON
 THE LANDSCAPE PLAN;
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved