Plan Review Notes
Plan Review Notes For Project Z17100014
Project Number Z17100014
Review Stop STORM
Sequence Number 1
Notes
Date Text
2017-11-03 15:51:35THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. REVIEW LOCATIONS OF PROPOSED TREES AND UNDERGROUND
 UTILITIES. ROOT BARRIERS ADJACENT TO THE UTILITIES MAY
 BE NECESSARY.
  
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE A COPY OF THE MODIFICATION TO THE SFWMD ERP
 PERMIT AND SIGNED AND SEALED DRAINAGE CALCULATIONS.
  
 3. PROVIDE A COPY OF THE MODIFICATION TO THE NPBCID
 PERMIT.
  
 4. CONSIDER CONNECTING THE DRAINAGE PIPE PROPOSED IN
 THE AREA EAST OF RIGHT FIELD TO THE PROPOSED DRAINAGE
 STRUCTURE IN THE EXPANDED DETENTION AREA INSTEAD OF TO
 THE EXISTING INLET SOUTH OF THE DETENTION AREA TO AVOID
 HAVING TO MODIFY THE EXISTING INLET TO ACCEPT THE PIPE.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  