Plan Review Notes
Plan Review Notes For Project Z17090003
Project Number Z17090003
Review Stop B
Sequence Number 2
Notes
Date Text
2019-02-12 20:26:12DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 PROPOSED MAJOR SUBDIVISION ONLY. IT IS NOT A REVIEW FOR
 FULL COMPLIANCE WITH FLORIDA BUILDING CODE.
  
 2. BUILDING LOCATION RELATIVE TO THE PROPOSED PROPERTY
 LINES. THE SUBMITTED JUSTIFICATION STATEMENT,
 DEVELOPMENT PROPOSAL SECTION STATES THAT THE PROPOSAL
 IS TO COMBINE THE 7 LOTS INTO 2 LARGER LOTS. HOWEVER,
 THE SUBMITTED SURVEY APPEARS TO SHOW THE 7 LOTS
 COMBINED INTO 1 LOT. IF THAT IS CORRECT, THE FOLLOWING
 COMMENT WILL IS NOT APPLICABLE.
  
 3. THIS COMMENT DOES IS NOT APPLICABLE IF THE PROPOSAL
 IS TO COMBINE THE 7 LOTS INTO 1 LOT. IF THE PROPSAL IS
 TO COMBINE THE 7 LOTS INTO 2 LOTS, THE SURVEY SHOULD
 SHOW THE 2 LOTS. WHEREVER THE LOT LINE IS PLACED TO
 SEPARATE THE 2 LOTS, THE FIRE RATING AND PERCENTAGE OF
 UNPROTECTED OPENINGS IN THE BUILDING WALLS CLOSE TO
 THAT LOT LINE SHALL BE COMPLY WITH TABLE 602, SECTION
 705, AND TABLE 705.8, OF FLORIDA BUILDING CODE. TO
 DEMONSTRATE THAT COMPLIANCE, A DRAWING WOULD HAVE TO BE
 SUBMITTED SHOWING THE WALL FIRE RESISTANCE RATING,
 PERCENTAGE OF UNPROTECTED OPENINGS, AND WHETHER THE
 BUILDINGS ARE FULLY FIRE SPRINKLER PROTECTED. NO
 INFORMATION HAS BEEN PROVIDED TO ASSERTAIN WHAT
 PERCENTAGE OF THE AFFECTED WALLS WOULD BE CONSIDERED
 "UNPROTECTED OPENING" AND WHETHER THE BUILDINGS ARE
 FULLY SPRINKLER PROTECTED AS DEFINED BY NFPA 13.
  
  
 ROBERT BROWN
 BUILDING OFFICIAL