Plan Review Notes
Plan Review Notes For Project Z17080019
Project Number Z17080019
Review Stop STORM
Sequence Number 2
Notes
Date Text
2017-12-18 11:46:45THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 12/8/2017 REVIEW PACKAGE DISTRIBUTED BY LINDA LOUIE.
 UNLESS OTHERWISE NOTED, CHANGES TO THE PLANS CAN BE
 MADE AT TIME OF ENGINEERING PERMIT SUBMIITAL.
  
 1. A COUPLE OF THE CITY'S STANDARD DETAILS (GC-1, GC-5)
 HAVE LATER REVISION DATES THAN THE ONES IN THE CURRENT
 PLANS. INCLUDE THE LATEST CITY DETAILS WITH THE PLANS.
  
 2. ARE PRB'S PROPOSED IN THE DRAINAGE STRUCTURES
 ATTACHED TO EXFILTRATION TRENCHES? IF SO, PROVIDE A
 DETAIL FOR THE PRB IN THE PLANS AND THE CONSULTANT'S
 EXFILTRATION TRENCH TYPICAL DETAILS ON SHEET PE-2.2
 WILL NEED TO BE REVISED TO SHOW A SUMP DEEPER THAN 12".
  
 3. NOTE CONCRETE STRENGTH FOR MONOLITHIC SIDEWALK
 (2,500 PSI) IS DIFFERENT THAN SIDEWALK STRENGTH IN
 DETAIL GC-1 (3,000 PSI).
  
 4. IN THE STORMWATER CALCULATIONS ON SHEET PE-2.2,
 THERE IS REFERENCE TO "0.06 ACRES OF ADDITIONAL
 IMPERVIOUS AREA (INCLUDING FUTURE PARKING". IT'S MY
 UNDERSTANDING THERE IS NO LONGER A FUTURE PARKING LOT.
 PLEASE REVISE THIS NOTE TO REFLECT THIS.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]