2018-05-10 18:03:24THE FOILLOWING COMMENTS ARE FROM THE REVIEW OF THE MAY
 7, 2018 SUBMITTAL PACKAGE.
  
 1. THE LANDSCAPE PLANS ARE NOT SHOWING THE LATEST
 PROPOSED UTILITIES SHOWN ON THE CIVIL PLANS. INCLUDE
 THE ROOF DRAINAGE PIPING ON THE PLUMBING SITE PLAN .
  
 2. LABEL VERTICAL DATUM ON DRAINAGE PLAN AND WATER AND
 SEWER PLANS. PROVIDE CONVERSION EQUATION TO NGVD 1929.
  
 3. IDENTIFY WHICH DRAINAGE STRUCTURE(S) WILL BE CONTROL
 STRUCTURES FOR RESTRICTING RUNOFF DISCHARGE FROM THE
 SITE.
  
 4. DDA NEEDED AFTER THE 8" GATE VALVE ON THE WATER MAIN
 AT THE NORTHEAST CORNER OF THE PROPERTY. THE WATER MAIN
 AFTER THE VALVE WILL BE A PRIVATE WATER MAIN.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER