2018-05-10 12:27:54BELOW ARE OUTSTANDING SITE PLAN COMMENTS (PLANS REVISED
 AND SUBMITTED TO CITY ON 5/3/18) IN ASSOCIATION WITH
 THE REQUEST FOR THE MAJOR PLANNED DEVELOPMENT (PD)
 AMENDMENT, APPROVED BY THE CITY COMMISSION ON 1/29/18
 (ORDINANCE NO. 4757-17).
  
 1.) PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE COVER
 SHEET: LIFE SAFETY PLAN-GROUND LEVEL IS SHEET A1.06
 (NOT A1.07); LIFE SAFETY PLAN-TYPICAL LEVEL IS SHEET
 A1.07 (NOT A1.05); LIFE SAFETY PLAN-ROOF LEVEL IS SHEET
 A1.08 (NOT A1.05); TREE DISPOSITION PLAN IS SHEETS TD-1
 AND TD-2 (NOT TDP-1 AND TDP-2); PLUMBING SITE PLAN IS
 SHEET P-100 (NOT MECHANICAL SITE PLAN);.
  
 2.) SHEET A0.02 IS INCONSISTENT WITH THE LATEST CHANGES
 MADE TO THE SITE PLAN (I.E. LOCATION OF THE LIGHT
 FIXTURES, TREES IN THE MIDDLE OF THE PARKING AREA
 PEDESTRIAN CROSSWALK, PAVED SURFACE IS SHADED GREEN
 WITHIN THE CROSSWALK, ETC.). PLEASE ADDRESS.
  
 3.) PLEASE ADDRESS THE FOLLOWING IN THE PROJECT
 INFORMATION TABULAR ON SHEET A0.03: THE BUILDING
 HEIGHT INFORMATION DOES NOT MATCH THE HEIGHT PROVIDED
 IN THE BUILDING ELEVATIONS (SHEETS A2.01 AND A2.02);
 SIDE SETBACK (WEST) IS 43'-9" (NOT 43'-9""); PLEASE
 MODIFY THE FOOTNOTE REGARDING THE 40% REDUCTION TO
 REFERENCE THE ZONING CODE SECTION OR ORDINANCE NO.
 4758-17 (THE CITY-INITIATED TEXT AMENDMENT HAS ALREADY
 BEEN ADOPTED).
  
 4.) THE BICYCLE RACK DETAIL ON SHEET A0.04 HAS BEEN
 MODIFIED SO THAT IT IS NO LONGER CONSISTENT WITH THE
 CITY'S BICYCLE PARKING GUIDELINES. PLEASE ADDRESS AS
 THE WAVE RACK IS NOT PERMITTED IN THE CITY.
  
 5.) PLEASE CORRECT THE PROPERTY NAME AND PROPERTY
 ADDRESS FOR DETAIL 0.6 ON SHEET A0.05 (MONUMENT SIGN
 DETAILS).
  
 6.) ADD NOTE TO SEE DETAIL ON SHEET A0.05 AT THE
 LOCATION OF THE MONUMENT SIGN ON SHEET A1.01 (SITE
 PLAN).
  
 7.) GENERAL SITE PLAN NOTE #5 ON SHEET A1.01 (SITE
 PLAN), STATES THAT THE SANITARY LINE WILL BE CONNECTED
 TO THE ADJACENT PROPERTY LIFT STATION. PER CONDITION OF
 APPROVAL IN ORDINANCE NO. 4757-17, THE DEVELOPER SHALL
 PROVIDE AN AGREEMENT FOR THE CONNECTION. PLEASE
 ADDRESS.
  
 8.) GENERAL SITE PLAN NOTE #12 SHOULD STATE THAT THERE
 SHALL NOT BE ANY LANDSCAPE MATERIAL WITHIN 5 FT. OF
 UNDERGROUND UTILITIES (NOT LOCATED WITHIN 5 FT. OF
 UNDERGROUND UTILITIES). PLEASE CORRECT.
  
 9.) ALL EXTERIOR LIGHTING SHALL BE SHIELDED TO REDUCE
 GLARE AND SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE
 AWAY FROM ALL ADJACENT RESIDENTIAL DISTRICTS, ADJACENT
 RESIDENCES OR PUBLIC THOROUGHFARES. PLEASE REVIEW
 PHOTOMETRIC PLAN AND ENSURE THE PLAN DEMONSTRATES
 COMPLIANCE. PLEASE ADD NOTE IN THE PHOTOMETRIC PLAN IF
 CONSISTENT WITH THE ZLDR FOR EXTERIOR LIGHTING. [ZLDR
 S.94-309(A)]
  