2017-10-16 16:54:46THE FOLLOWING COMMENTS ARE BASED UPON THE REVIEW OF THE
 OCTOBER 5, 2017 SUBMITTAL PACKAGE.
  
 1. LABEL THE VERTICAL DATUM ON THE CONCEPTUAL PAVING,
 DRAINAGE, WATER AND WASTEWATER PLAN. IF DIFFERENT THAN
 CITY'S VERTICAL DATUM, NGVD1929, THEN PROVIDE
 CONVERSION FACTOR TO OBTAIN NGVD 1929.
  
 2. SHOW ALL UTILITIES ON THE LANDSCAPE PLANS. THE
 CONCEPTUAL ENGINEERING PLAN SHOWS STORM WATER PIPES
 INTO THE DRY DETENTION AREA THAT ARE NOT SHOWN ON THE
 LANDSCAPE PLANS.
  
 3. CONCEPTUAL ENGINEERING PLAN LABELS THE OPEN FEATURE
 IN THE SOUTHWEST CORNER OF THE SITE AS A PROPOSED DRY
 DETENTION AREA. THE ARCHITECTURAL PLANS LABEL THE AREA
 AS RETENTION POND. POND INDICATES PERMANENT WATERBODY
 WHICH IS NOT THE SAME AS DRY DETENTION AREA. RETENTION
 AND DETENTION ARE NOT THE SAME EITHER.
  
 4. SFWMD HAS MINIMUM DIMENSIONAL REQUIREMENTS FOR WET
 PONDS USED FOR WATER QUALITY TREATMENT.
  
 5. SFWMD PERMIT TO BE SUBMITTED WITH ENGINEERING PERMIT
 APPLICATION.
  