| Date |
Text |
| 2017-10-06 14:25:21 | CITY OF WEST PALM BEACH |
| | ENGINEERING SERVICES DEPARTMENT |
| | DATE: 10/06/2017 |
| | PROJECT: GEORGIAN GARDENS APARTMENT |
| | ADDRESS: 4330 COMMUNITY DRIVE |
| | STATUS: FAILED |
| | |
| | THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL |
| | DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION |
| | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE |
| | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT |
| | APPLICATION PROCESSES. FOLLOWING COMMENTS NEED TO BE |
| | ADDRESSED PRIOR TO SITE PLAN APPROVAL: |
| | |
| | 1. NOTE NO. 2 SHOULD SAY, 'ALL WATER AND WASTEWATER |
| | CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE CITY OF |
| | WEST PALM BEACH ENGINEERING SERVICES DEPARTMENT...' |
| | |
| | 2. PLACEMENT OF ANY PROPOSED METER, BACKFLOW PREVENTER, |
| | DCDA, CITY?S POINT OF SERVICE, ETC. SHALL BE INSTALLED |
| | PER THE CITY?S STANDARD DETAILS. WATER METER SHOULD BE |
| | WITHIN THE RIGHT-OF-WAY OR INSIDE AN 'UTILITY EASEMENT' |
| | JUST INSIDE THE PROPERTY NEAR THE RIGHT-OF-WAY AND |
| | ACCESSIBLE; |
| | |
| | 3. AS-BUILTS SHOWS ANOTHER 8-INCH SANITARY SEWER PIPE |
| | WITH A MANHOLE ON THE SOUTH SIDE OF THE PROPERTY |
| | CONNECTING TO THE ADJACENT PROPERTY'S LIFT STATION. |
| | NEEDS TO BE VERIFIED AND FOR AS-BUILT INFORMATION |
| | CONTACT JANICE TARBILL AT [email protected]; |
| | |
| | 4. CHANGE DDCV TO DCDA AND RPZ TO RPPA; |
| | |
| | 5. CITY DOES NOT ALLOW DIRECTIONAL BORE OF UTILITIES |
| | WILL NEED TO REFER TO CITY STANDARD DETAIL P-4 |
| | TRENCH-BACKFILL-PAVEMENT RESTORATION; |
| | |
| | 6. THE CITY WILL NEED A COPY OF THE AGREEMENT WHICH |
| | ALLOWS GEORGIAN GARDENS TO CONNECT TO THE ADJACENT |
| | PROPERTY'S FIRE LINE AND DRIVEWAY; |
| | |
| | 7. SUBMIT ESTIMATES FOR WATER AND FIRE DEMAND, BOTH |
| | AVERAGE AND PEAK FLOW WITH PEAKING FACTOR. ALSO SUBMIT |
| | ESTIMATES OF SANITARY SEWER FLOW FOR THE PROPOSED |
| | DEVELOPMENT. SHOW PROJECTED DEMANDS ON THE UTILITY PLAN |
| | SHEET; |
| | |
| | 8. THE AVAILABLE WATER PRESSURE IN THIS PORTION OF THE |
| | CITY MAY NOT BE ACCEPTABLE AT ELEVATIONS HIGHER THAN |
| | THE 2ND FLOOR. WE RECOMMEND A LONG-TERM PRESSURE STUDY |
| | BE PERFORMED PRIOR TO FINALIZATION OF THE UTILITY |
| | DESIGN; |
| | |
| | 9. ON THE LANDSCAPING PLAN, ROOT BARRIERS MAY BE |
| | REQUIRED WHERE PLANTINGS ARE NEAR UNDERGROUND |
| | STORMWATER, SANITARY, OR POTABLE WATER LINES; |
| | |
| | AFTER THE SITE PLAN IS APPROVED, IN THE NEXT PHASE, THE |
| | FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR TO |
| | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING |
| | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL: |
| | |
| | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL |
| | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. |
| | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS |
| | CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK: |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC |
| | CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF |
| | WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL |
| | WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE |
| | FOLLOWING LINK: |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | 3. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL |
| | APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND |
| | SANITARY SEWER CALCULATION (IN DETAIL I.E. AVERAGE AND |
| | PEAK WITH PEAKING FACTOR). SUBMIT CALCULATIONS TO |
| | VALIDATE METER SIZE SELECTION. SHOW THESE CALCULATIONS |
| | ON THE UTILITY PLAN SHEET AS WELL; |
| | |
| | 4. SHOW ON THE FINAL PLANS WHERE ARE THE PROPOSED WATER |
| | AND SANITARY SEWER LINES ARE CONNECTED TO EXISTING |
| | WATER AND SEWER MAINS; |
| | |
| | 5. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE |
| | CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE |
| | DETAIL SHEET/S DURING SUBMISSION OF THE FINAL |
| | ENGINEERING PLANS. CONTACT THE ENGINEERING SERVICES |
| | DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD |
| | FORMAT. CITY?S STANDARD DETAILS (IN PDF FILE FORMAT) |
| | CAN BE DOWNLOADED FROM THE FOLLOWING SITE: HTTP://WPB.O |
| | RG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS- |
| | APPLICATIONS |
| | |
| | 6. IN THE FINAL PLANS, MUST PROVIDE UTILITY CONFLICT |
| | TABLE (BOTTOM AND TOP OF CROSSING PIPES) AT THE |
| | CONFLICT POINTS OF ALL WATER, STORM AND SANITARY SEWER |
| | PIPES AS WELL AS OTHER FRANCHISE UTILITIES. EXISTING |
| | UTILITIES WITHIN THE PROPOSED SANITARY SEWER LATERAL |
| | ARE TO BE VERIFIED VIA SOFTDIGS, PROVIDE ALL UTILITY |
| | CROSSING INFORMATION; |
| | |
| | 7. IN THE FINAL PLANS, SHOW DIRECTION OF FLOW FOR THE |
| | EXISTING SANITARY SEWER. SHOW INVERT AT CONNECTION |
| | POINTS AND INCLUDE A PROFILE FOR THE PROPOSED SERVICE |
| | LATERAL WITH GROUND ELEVATIONS ABOVE THE PIPE; |
| | |
| | 8. PAVEMENT RESTORATION FOR OPEN CUT/TRENCH FOR UTILITY |
| | CONNECTION WORKS WILL NEED TO BE IN ACCORDANCE WITH |
| | 2016 CITY STANDARD DETAIL GC-9. THE ROAD SHALL BE |
| | MILLED/RESURFACED FOR FULL LANE WIDTH OF THE TRAVEL |
| | LANE(S) ENCROACHED BY THE TRENCH AREA, INCLUDING A |
| | TRANSITION AREA OF 50 FEET ON EACH SIDE OF THE TRENCH. |
| | PLEASE SHOW ON THE FINAL PLANS THE EXTENT OF THE |
| | MILLING AND RESURFACING; |
| | |
| | 9. SHOW ON THE FINAL PLANS SIZE AND MATERIAL OF ALL |
| | EXISTING UTILITIES ON COMMUNITY DRIVE INCLUDING BUT NOT |
| | LIMITED TO WATER, SEWER, GAS, UNDERGROUND ELECTRIC |
| | CONDUITS ETC. PLEASE IDENTIFY THE SOURCE OF THE |
| | AS-BUILT INFORMATION UTILIZED FOR THE POTABLE WATER, |
| | SANITARY SEWER, AND STORM SEWER DESIGN; |
| | |
| | 10. FOR THE FINAL WATER AND SEWER PLANS, INCLUDE A NOTE |
| | THAT: AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM |
| | BEACH CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD |
| | FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW: HT |
| | TP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICA |
| | TIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
| | |
| | 11. ALL PROPOSED FIRE DEPARTMENT CONNECTIONS SHALL BE |
| | WITHIN 100 FEET OF A FIRE HYDRANT AND SHALL BE WITHIN |
| | AN EASEMENT WITHIN THE PROPERTY. |
| | |
| | SOFIA QUINONES-BENEJAM, EI |
| | PROJECT ENGINEER |
| | CITY OF WEST PALM BEACH |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33402 |
| | (MAILING ADDRESS: PO BOX 3366) |
| | P: 561.494.1108 |
| | C: 561.459.6518 |
| | F: 561.494.1116 |
| | EMAIL: [email protected] |
| | |
| |
Print |