2017-09-20 11:04:07DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. ACCESSIBLE ROUTE FROM SIDEWALK/RIGHT-OF-WAY TO THE
 BUILDING ENTRANCE. SHEETS SP-1 AND LP-2 DO NOT SHOW A
 WHEELCHAIR AND PEDESTRAIN ROUTE FROM THE SIDEWALK TO
 THE BUILDING ENTRANCE. WHEN SUBMITTED FOR PERMIT, THE
 PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE ROUTE,
 COMPLYING WITH SECTIONS 206.2 AND 402.2 OF FLORIDA
 ACCESSIBILITY CODE, FROM THE PUBLIC RIGHT-OF-WAY TO ALL
 ACCESSIBLE BUILDING OR FACILITY ENTRANCES.
  
 3. DISTRIBUTION OF ACCESSIBLE PARKING SPACES. SITE PLAN
 SHEET SP-1 SHOWS MORE THAN 50 PARKING SPACES SERVING
 THIS BUILDING AND REMOTE FROM THE OTHER BUILDINGS IN
 THE PLAZA, BUT ONLY SHOWS TWO ACCESSIBLE PARKING SPACES
 NEAR THE PROPOSED BUILDING. WITH THE NUMBER OF PARKING
 SPACES SHOW, THREE ACCESSIBLE PARKING SPACES ARE
 REQUIRED CLOSE TO THE ENTRANCE FACADE OF THE PROPOSED
 BUILDING. THE TOTAL NUBER OF ACCESSIBLE SPACES IN THE
 PARKING LOT IS SUFFICIENT, SO THIS COULD BE ACHIEVED BY
 RELOCATING AN ACCESSIBLE PARKING SPACE IF THE OWNER
 PREFERS NOT TO ADD ANOTHER ACCESSIBLE PARKING SPACE.
 PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE,
 ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE
 SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN
 OF ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION
 502 OF FLORIDA ACCESSIBILITY CODE
  
 4. BUILDING HEIGHT, AREA AND OCCUPANCY CLASSIFICATION.
 WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 6. GREASE INTERCEPTOR. IF ANY OF THE PROPOSED UNITS
 WILL BE OCCUPIED BY A RESTAURANT, A GREASE INTERCEPTOR
 WILL BE REQUIRED. PLEASE CONTACT JEFFREY ODOMS,
 UTILITIES O&M SUPERINTENDENT, PUBLIC UTILITIES
 DEPARTMENT, FATS OILS AND GREASE DIVISION, AT (561)
 822-2172, OR BY EMAIL: [email protected]
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 8. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 9. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES
 (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF
 PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT
 SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT
 (561) 822-1521, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  