2017-12-07 15:23:22THE COMMENTS BELOW ARE FROM THE REVIEW OF THE
 11/27/2017 SUBMITAL PACKAGE FROM THE PLANNER P.
 GREILICH:
  
 1. THE VERTICAL DATUM ON THE SURVEY IS NAVD 1983. THE
 CITY USES NGVD 1929 AS THE VERTICAL DATUM. PROVIDE ON
 THE SURVEY THE CONVERSION FACTOR BETWEEN NAVD 1983 AND
 NGVD 1929.
  
 2. THE NEW CURB ON THE EAST SIDE OF THE PROPOSED
 GENERATOR ENCLOSURE APPEARS TO ENCROACH INTO A PARKING
 SPACE THAT IS TO REMAIN. VERIFY THERE WILL BE
 SUFFICIENT SPACE FOR A PARKING SPACE ADJACENT TO THE
 ENLARGED LANDSCAPE ISLAND.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  