Plan Review Notes
Plan Review Notes For Project Z17070013
Project Number Z17070013
Review Stop STORM
Sequence Number 2
Notes
Date Text
2017-12-06 15:21:59THE COMMENTS BELOW ARE FROM THE REVIEW OF THE NOVEMBER
 28, 2017 SUBMITTAL PACKAGE:
  
 1. SHOW SIDEWALK REPAIR AND PAVEMENT MILLING AND
 OVERLAY FOR THE WATER SERVICE TAP.
  
 2. PROVIDE SPOT GRADES AT THE BACK OF DIXIE HWY
 SIDEWALKS FOR THE DRIVEWAYS. THE BACK OF WALK ELEVATION
 SHOULD BE HIGHER THAN THE GRATE ELEVATION OF THE
 NEAREST CATCH BASIN BEHIND THE SIDEWALK.
  
 3. CONNECT ROOF DRAINS TO THE DRAINAGE INLETS.
  
 4. IT APPEARS THERE IS A TRENCH DRAIN ACROSS THE SOUTH
 DRIVEWAY AT THE PROPERTY LINE. PLEASE ADVISE IF THIS
 WILL BE CONSTRUCTED.
  
 5. THE FRONT DISPLAY AREA IS TO DRAIN INTERNALLY AND
 NOT TO THE SIDEWALK.
  
 6. LABEL THE VERTICAL DATUM ON THE ENGINEEERING PLANS
 AND PROVIDE THE CONVERSION FACTOR TO NGVD 1929 IF THE
 VERTICAL DATUM IS DIFFERENT FROM NGVD 1929. (REPEAT
 COMMENT).
  
 7. CONFIRM AN 8" DCDA IS APPROPRIATE FOR A 4" FIRE
 LINE.
  
 8. ON THE SITE PLAN SHEET SP-1, THE DIMENSION LINE
 ACROSS THE SOUTH DRIVEWAY APPROXIMATELY 50 FEET FROM
 THE EAST PROPERTY LINE IS DRAWN FROM THE FACE OF THE
 NORTH CURB TO THE BACK OF THE SOUTH CURB AND SHOWS A
 DIMENSION OF 19.8 FEET. THE RESPONSE TO PREVIOUS
 SIMILAR COMMENT WAS THE DIMENSION WAS FROM BACK OF CURB
 TO BACK OF CURB.
  
 TRACY L. WARD, P.E.
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120