Plan Review Notes
Plan Review Notes For Project Z17070013
Project Number Z17070013
Review Stop TRAFFIC
Sequence Number 1
Notes
Date Text
2017-09-15 17:01:54 
 THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS WILL BE REVIEWED AS PART OF THE ENGINEERING
 DEVELOPMENT APPROVAL AND BUILDING PERMIT APPLICATION
 PROCESS. THE FOLLOWING COMMENTS NEED TO BE ADDRESSED
 PRIOR TO SITE PLAN APPROVAL:
  
 1) PROPOSED PARKING LOT AISLE WIDTH IS 25'. CITY
 STANDARD IS 24'. REDUCING TO STANDARD AISLE WIDTH WOULD
 ALLOW FOR MORE LANDSCAPING AND LESS IMPERVIOUS AREA.
 2) PROPOSED PARKING LOT STALL DEPTH IS 18.5'. CITY
 STANDARD DEPTH IS 18'. REDUCING TO STANDARD AISLE WIDTH
 WOULD ALLOW FOR MORE LANDSCAPING AND LESS IMPERVIOUS
 AREA.
 3) SOUTH DRIVEWAY DOES NOT MEET FDOT SEPARATION OF
 ACCESS POINT CRITERIA AND CITY SEPARATION CRITIERA
 (SECTION 94-312) WITH RESPECT TO ADJACENT RESTARAUNT
 DRIVEWAY.
 4) PROPOSED SITE PLAN EXCEEDS MAXIMUM NUMBER OF ACCSS
 POINTS TO STREET. MAXIMUM ALLOWED ACCESS POINTS IS ONE.
 (SECTION 94-312).
 5) ELIMINATE ONE ACCESS ON S. DIXIE. PREFERABLY THE
 SOUTH ACCESS POINT.
 5) S. DIXIE IS A FDOT ROAD. ANY MODIFICATIONS TO THE
 ACCESS POINTS WILL REQUIRE FDOT PERMIT AND APPROVAL.
 PROVIDE STATUS OF FDOT COORDINATION AT PPRC.
 6) PROVIDE COUNTY TRAFFIC CONCURRENCY LETTER.
 7) THE SIGHT TRIANGLE SHOWN ON THE SITE FOR THE S. DIXE
 ENTRANCE NEEDS TO MEET FDOT CRITERIA.
 8) REVIEW EXISTING DRIVEWAY APRON FOR A.D.A.
 COMPLIANCE.
  
 ERIK D. FERGUSON, P.E.
 SENIOR PROJECT ENGINEER
 561-494-1092
 [email protected]