Plan Review Notes
Plan Review Notes For Project Z17060018
Project Number Z17060018
Review Stop STORM
Sequence Number 3
Notes
Date Text
2017-12-06 16:31:10THE COMMENTS BELOW ARE FROM THE REVIEW OF THE
 ENGINEERING PLANS AND SURFACE WATER MANAGEMENT
 CALCULATIONS SIGNED AND SEALED BY RONALD W. LAST, P.E.
 ON 12/1/2017:.
  
 1. SHOW MILL AND RESURFACE LIMITS FOR UTILITY TRENCH
 CUTS IN THE ROADWAY ON THE ENGINEERING PLANS.
  
 2. PROVIDE CROSS SECTION FOR DRIVEWAY APRON SHOWING
 CROSS SLOPES AND MINIMUM 4 FEET WIDTH AT 2 PERCENT
 CROSS SLOPE TO MEET ADA CRITERIA FOR SIDEWALK.
 REMAINING DRIVEWAY SLOPE SHOULD NOT EXCEED 8% PER CITY
 STANDARD DETAIL GC-7.
  
 3. EXISTING GRADES FOR TUXEDO LANE SHOW THE NORTH BOUND
 LANES SLOPE TOWARD THE PROJECT. INDICATE A SWALE
 BETWEEN THE SIDEWALK AND EDGE OF PAVEMENT AND PROVIDE
 TYPICAL CROSS SECTION FROM BACK OF WALK TO EDGE OF
 PAVEMENT. INVERT OF SWALE DOES NOT NEED TO BE MORE THAN
 3 INCHES BELOW EDGE OF PAVEMENT. SWALE WON'T BE NEEDED
 IN DRIVEWAY BUT EDGE OF PAVEMENT SHOULD SLOPE ALONG
 DRIVEWAY TO CONVEY WATER TO THE SIDE(S) OF THE
 DRIVEWAY. SWALE LONGITUDINAL SLOPE CAN FOLLOW THE SLOPE
 OF THE ROAD (I.E. FROM SOUTH TO NORTH).
  
 4. INVERT FOR MH#2 APPEARS TO BE LABELED WITH THE WRONG
 DIRECTION.
  
 5. INDICATE IF A RETAINING WALL WILL BE NEEDED ALONG
 THE EAST PROPERTY LINE. THERE IS A 4 FOOT DROP FROM THE
 EXISTING GRADE ALONG THE PROPERTY LINE TO PROPOSED
 INTERIOR GRADES.
  
 6. PROVIDE BACKUP FOR THE EXFILTRATION RATES SHOWN IN
 THE SURFACE WATER MANAGEMENT CALCULATIONS.
  
 7. EXFILTRATION STORAGE DOES NOT REACH 0.08 AC-FT UNTIL
 STAGE 15.5 FEET NAVD, WHEN H2 IS 8.50 FEET.
  
 TRACY L. WARD, P.E
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120