Plan Review Notes
Plan Review Notes For Project Z17050039
Project Number Z17050039
Review Stop STORM
Sequence Number 1
Notes
Date Text
2017-06-20 15:18:59THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS WERE GENERATED FROM THE REVIEW
 OF THE PLANS INCLUDED IN THE JUNE 8, 2017 REVIEW
 PACKAGE:
  
 1. LABEL THE VERTICAL DATUM ON THE GRADING AND DRAINAGE
 PLAN SHEET AND SECTIONS SHEET.
  
 2. COVER SHEET OF ENGINEERING PLANS INDICATE THE
 VERTICAL DATUM IS NAVD 1988. THE CITTY'S DATUM IS NGVD
 1929. PROVIDE THE CONVERSION BETWEEN THE TWO VERTICAL
 DATUMS WHEREVER NAVD 1988 IS SHOWN.
  
 3. INDICATE WHAT WILL HAPPEN TO THE TEST WELL.
  
 4. THE LANDSCAPE PLAN SHOWS INLETS AND STORM PIPE FOR
 THE DRY RETENTION AREA. THESE ARE NOT SHOWN ON THE
 ENGINEERING PLANS. THE UTILITIES SHOWN ON THE LANDSCAPE
 PLANS AND ENGINEERING PLANS SHOULD MATCH.
  
 5. INDICATE IF PROJECT AREA IS SUBJECT TO THE C-51
 BASIN RULE FOR FILL WITHIN THE FLOOD PLAIN.
  
 6. PROVIDE DRAINAGE CALCULATIONS SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEERING DEMONSTRATING THE PROJECT
 MEETS SFWMD CRITERIA FOR WATER QUALITY AND WATER
 QUANTITY RUNOFF.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  