Plan Review Notes
Plan Review Notes For Project Z17040019
Project Number Z17040019
Review Stop STORM
Sequence Number 3
Notes
Date Text
2017-09-25 15:31:11THE FOLLOWING NOTES ARE BASED ON THE REVIEW OF THE
 RESUBMITTAL PACKAGE FROM ES, DATED AUGUST 31, 2017.
  
 1. APPLICANT HAS INDICATED THE PROPOSED DEVELOPMENT
 AREA WILL NOT BE WITHIN A SPECIAL FLOOD HAZARD AREA AS
 SHOWN ON THE NOW ADOPTED FEMA FIRMS.
  
 2. VERTICAL DATUM CONVERSION BETWEEN NAVD1988 AND
 NGVD1929 ARE NOW CONSISTENT BETWEEN THE TOPOGRAPHIC
 SURVEY AND PRELIMINARY ENGINEERING PLANS.
  
 3. WILL THE SIDEWALK ALONG CECIL AVE. BE AT GRADE? HOW
 RUNOFF FROM SOUTH SIDE OF CECIL AVE. MAKE IT INTO THE
 SWALE, SOUTH OF THE ROADWAY?
  
 4. DRY DETENTION BASINS ARE CALLED OUT ON THE
 PRELIMINARY ENGINEERING PLANS. HOWEVER THEY ARE LABELED
 AS DRY RETENTION ON THE OTHER PLANS (SITE PLAN, MASTER
 PLAN, LANDSCAPE PLANS).
  
 5. EXPLAIN HOW THE DRY DETENTION AREA WILL BE USED FOR
 DRAINAGE. THE DRY DETENTION BASIN AT THE SOUTH END OF
 THE FOOTBALL FIELD IS LOCATED AT THE UPSTREAM END OF
 THE STORM WATER SYSTEM. A CONTROL STRUCTURE IS NOT
 IDENTIFIED ON THE PLANS TO BACKUP THE WATER INTO THE
 DRY DETENTION BASIN. EXPLAIN HOW STORMWATER QUALITY
 TREATMENT WILL BE OBTAINED.
  
 6. IN ADDITION TO MODIFYING THE SFWMD PERMIT, A PERMIT
 MODIFICATION WILL BE NEEDED FROM THE NORTHERN PALM
 BEACH COUNTY IMPROVEMENT DISTRICT.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]