| 2017-05-10 12:38:00 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. NEW FLOOD INSURANCE RATE MAPS (FIRMS) WILL BE |
| | ADOPTED BEFORE OCTOBER 2017. THE PROPOSED BUILDING MAY |
| | BE IN FLOOD ZONE. THE CURRENT REQUIREMENT IS FOR THE |
| | ELEVATION OF THE FIRST FLOOR OF THE BUILDING AND ALL |
| | ASSOCIATED MECHANICAL EQUIPMENT (CHILLERS, GENERATORS |
| | ETC.) SHALL BE 12 INCHES (FREEBOARD) ABOVE THAT BASE |
| | FLOOD ELEVATION. PLEASE NOTE THAT THERE IS A PROPOSAL |
| | TO INCREASE THE FREEBOARD TO 24 INCHES SOMETIME AFTER |
| | THE MIDDLE OF MAY 2017. |
| | |
| | 3. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, |
| | ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A |
| | PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND |
| | DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA |
| | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 |
| | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE). COMMENT TO |
| | BE ADDRESSED WHEN SUBMITTING FOR PERMITTING. |
| | |
| | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, |
| | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, |
| | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE |
| | FLORIDA BUILDING CODE |
| | |
| | 5. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, |
| | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, |
| | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, |
| | SITE IRRIGATION, ETC. |
| | |
| | 7. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE |
| | ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, |
| | GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |