| Date |
Text |
| 2017-04-11 19:50:39 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. NUMBER OF ACCESSIBLE PARKING SPACES. SHEET SP-2, |
| | SITE PLAN, SHOWS 216 PARKING SPACES IN PARKING |
| | STRUCTURE 1, BUT SHOWS ONLY 6 ACCESSIBLE PARKING |
| | SPACES. 7 ACCESSIBLE PARKING SPACES ARE REQUIRED. THE |
| | MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES PROVIDED |
| | SHALL BE IN ACCORDANCE WITH SECTION 208.2 OF FLORIDA |
| | ACCESSIBILITY CODE. |
| | |
| | 3. ADMINISTRATION BUILDING FLOOR PLAN SHOWS NO INTERIOR |
| | CONNECTION BETWEEN THE LOUNGE AREA AND THE |
| | ADMINISTRATIVE OFFICES. AS A RESULT THE ADMINISTRATIVE |
| | OFFICES HAVE ONLY ONE EXIT DOOR. THERE ARE NO |
| | DIMENSIONS OR SCALE SHOWN ON THE PLAN AT THIS STAGE |
| | BUT, DEPENDING ON THE TRAVEL DISTANCES AND THE NUMBER |
| | OF OCCUPANTS, ANOTHER EXIT DOOR MAY BE REQUIRED. |
| | |
| | 4. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE |
| | |
| | 5. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. THE |
| | EQUIVALENT REQUIREMENTS FOR ONE AND TWO FAMILY |
| | DWELLINGS, AND TOWNHOUSES ARE IN SECTION R302 OF |
| | FLORIDA BUILDING CODE (RESIDENTIAL). |
| | |
| | 6. ENCLOSED PARKING GARAGES. IF THE PARKING STRUCTURES |
| | ARE ENCLOSED PARKING GARAGES AND DO NOT HAVE WALL |
| | OPENINGS, OR SUFFICIENT WALL OPENINGS TO MEET THE |
| | DEFINITION OF AN OPEN PARKING GARAGE, THEY WILL BE |
| | CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 8. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE |
| | ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, |
| | GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: |
| | [email protected] |
| | |
| | 9. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES |
| | (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF |
| | PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT |
| | SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT |
| | (561) 822-1521, OR BY EMAIL: [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |