2017-06-20 17:00:49THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE JUNE
 8, 2017 REVIEW PACKAGE:
  
 1. CLARIFY THE FOLLOWING IN THE STORMWATER STATEMENT:
 A. LINE 3.A - USE OF THE 0.9 RUNOFF COEFFICIENT IN THE
 FORMULA 0.9 X 1,200 FT2 X 1 INCH X 1 FT / 12 IN. THE
 VOLUME OF 1 INCH OF RUNOFF IS EQUAL TO 1 INCH TIMES THE
 AREA OF THE SITE.
  
 B. LINE 4.A AND 4.B - INDICATE ON THE SITE PLAN IN
 LOWER RIGHT OF SHEET WHERE THE SWALE DIMENSIONS WERE
 MEASURED. THE LENGTH OF THE FENCE ALONG THE WEST SIDE
 OF THE SITE MEASURES LESS THAN 300 FEET. THE DISTANCE
 BETWEN THE LEFT AND RIGHT TOP OF SLOPE MEASURED BETWEEN
 55 FEET AND 65 FEET. THE WIDTH OF THE BOTTOM OF THE
 SWALE MEASURES BETWEEN 5 FEET AND 7.5 FEET.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT