2017-09-05 14:38:01COMMENTS BELOW ARE BASED ON THE AUGUST 25, 2017 REVIEW
 PACKAGE:
  
 1. NO GRADING OR DRAINAGE PLAN WAS PROVIDED.
  
 2. NEW FEMA FIRM MAPS AND TWO FEET OF FREEBOARD ABOVE
 BASE FLOOD ELEVATION FOR STRUCTURES IN SPECIAL FLOOD
 HAZARD AREAS WILL BE EFFECTIVE ON OCTOBER 5, 2017 IF
 RESOLUTION PASSES AT SECOND READING BEFORE CITY
 COMMISSION.
  
 3. WATER & SEWER PLAN DRAWING DOES NOT MATCH THE SITE
 PLAN. THERE ARE TWO CURB LINES ALONG POINSETTIA AND
 EAST RIGHT-OF-WAY OF POINSETTIA IS SHOWN AT THE BACK OF
 WALK.
  
 4. STORM MANHOLE NEAR NORTHEAST CORNER OF POINSETTIA
 AVENUE AND 27TH STREET IS MISLABELED AS SANITARY SEWER
 MANHOLE ON THE WATER & SEWER PLAN.
  
 5. THERE IS A STORM SEWER PIPE LOCATED IN THE NORTH
 BOUND LANES OF POINSETTIA AVENUE THAT NEEDS TO BE SHOWN
 ON THE WATER & SEWER PLAN.
  
 6. DRIVEWAY APRONS SHOULD BE DESIGNED PER CITY STANDARD
 DETAIL.
  
 7. PROPOSED 2-INCH WATER SERVICE LINE WILL HAVE A
 CORPORATION STOP INSTEAD OF A GATE VALVE NEAR THE MAIN.
  
 8. REMOVE REFERENCES TO NSID IN THE UTILITY NOTES ON
 THE WATE R& SEWER PLAN.
  
 9. SHOW MILL AND OVERLAY LIMITS ON THE ENGINEERING
 DRAWING(S).
  
  
  