Plan Review Notes
Plan Review Notes For Project Z17020040
Project Number Z17020040
Review Stop STORM
Sequence Number 6
Notes
Date Text
2019-08-28 17:15:47THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 AUGUST 22, 2019 ROUTED SUBMITTAL PACKAGE.
  
 1. CONFIRM THERE WILL NOT BE A RAISED CURB BETWEEN THE
 PLANTERS ALONG N. DIXIE HWY AND THE ADJACENT SIDEWALK
 AND THAT RUNOFF FROM THE SIDEWALK WEST OF THE PLANTERS
 WILL BE ABLE TO FLOW INTO THE PLANTERS.
  
 2. PROVIDE VIDEO OF EXISTING STORM PIPES ON 4TH STREET.
 SOME PIPES MAY BE VCP. (REPEAT COMMENT)
  
 3. ADD THE CONVERSION EQUATION TO NGVD1929 TO GENERAL
 NOTE #7 ON THE COVER SHEET. (REPEAT COMMENT)
  
 4. CALL OUT THE TYPE OF CURB RAMPS AND ADA MATS FOR
 DRIVEWAYS CROSSING THE SIDEWALK ON 4TH STREET.(REPEAT
 COMMENT)
  
 5. CIVIL PLAN 5 SIGNING AND MARKING PLAN:
 A. PARKING DIMENSIONS DO NOT LINE UP WITH THE STRIPING
 ON 4TH STREET.(REPEAT COMMENT)
  
 6. PROVIDE DIMENSIONS AND ELEVATIONS (TOP AND BOTTOM OF
 TRENCH) OF THE EXFILTRATION TRENCHES
  
 7. DIFFERENT VERTICAL DATUMS REFERENCED ON THE CIVIL
 AND ARCHITECTURAL PLANS AND THE FFE'S VARY:
 CIVIL PLANS LIST FFE'S AS:
 A. 15.70 FEET NAVD88 FOR PROPOSED OFFICE TOWER
 B. 13.95 FEET NAVD88 FOR PROPOSED RESIDENTIAL TOWER
 C. 13.20 FEET NAVD88 FOR PROPOSED RETAIL BUILDING.
  
 THE ELEVATION VIEWS OF THE ARCHITECTURAL PLANS LIST
 FFE'S AS:
 A. 15 FEET 6 INCHES NGVD29 FOR THE PROPOSED OFFICE
 TOWER
 B. 13 FEET 9 INCHES NGVD29 FOR THE PROPOSED RESIDENTIAL
 TOWER
 C. 13 FEET 0 INCHES NGVD29 FOR THE PROPOSED RETAIL
 BUILDING.
  
 8. EAST ELEVATION ON SHEET A2.01 SHOWS 18 FEET 0 INCHES
 FROM THE LEVEL 2 PODIUM TO THE GROUND LEVEL BUT
 DIFFERENCE IN ELEVATIONS IS 10.5 FEET (33 FEET 6 INCHES
 MINUS 13 FEET 0 INCHES).
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120
  