2019-02-28 10:44:38OUTSTANTING COMMENTS FROM 5/11/17 REVIEW:
 4.NOT SATISFIED- PROPOSED CURB CUT ON 4TH STREET
 EXCEEDS THE MAXIMUM 25 FEEET IN WIDTH ALLOWED. THE 6
 FOOT WIDE MEDIAN IS STILL CONSIDERED PART OF THE CURB
 CUT.
 7 AND 8. SATISFIED
 9. NOT SATISFIED- CIVIL DRAWINGS (SHEET 9) SHOW RETAIL
 AREA AT ELEVATION 15.50 WHILE SIDEWALK IS AT ELEVATION
 APPROX. 12-13. SHEET 4 SHOWS RETAIL AT ELEVATION 13.
  
 OUTSTANDING COMMENTS FROM 11/27/19 REVIEW
 1. SATISFIED
 2. SATISFIED- PLEASE PROVIDE COLORED ELEVATIONS WITHOUT
 SHADES TO CLEARLY CONVEY THE DIFFERENT MATERIALS OF THE
 ELEVATION. PLEASE EXPLAIN WHAT IS THE DIFFERENCE
 BETWEEN THE PREVIOUS FACADE DETAIL AND THE PROPOSED.
 3. NOT SATISFIED - PLEASE CONSIDE LOCATING THE FIRE
 DEPARTMENT CONNECTION ON THE STAIR WALL OR LOCATE THEM
 CLOSER TO THE STAIR WALL. TEH FDC CONNECTION ON 4TH
 STREET IS ALSO LOCATED ON THE PEDESTRIAN PATH AREA.
 4. SATISFIED- PRINTING FOR LANDSCAPE DRAWINGS WAS NOT
 DONE TO PRESERVE THE SCALE. STAFF WAS NOT ABLE TO
 MEASURE INDICATED DIMENSIONS.
 5. NOT SATISFIED - LANDSCAPE MATERIALS HAVE
 SUBSTANTIALLY CHANGED FROM ORIGINAL APPROVAL IN
 DETRIMENT OF THE QUALITY OF THE PUBLIC REALM. SEE
 LANDSCAPE COMMENTS.
 6. SATISFIED- PLEASE DIMENSION PARKING SPACES TO
 CONFIRM COMPLIANCE WITH MINIMUM REQUIREMENTS. SPACE
 ADJACENT TO A WALL OR COLUMN SHALL BE WIDER (SEC
 94-111(C))
 7. NOT SATISFIED- PLEASE PROVIDE SECTIONS TO CONFIRM
 THE LEVELS ARE MAINTAINED . CURB CUT SHALL BE DESIGNED
 IN A WAY THAT THE SIDEWALK LEVEL IS MAINTAINED ACROSS
 CURB CUT AND NOT LOWERED TO THE ROAD LEVEL. PEDESTRIANS
 GET PRIORITY, NOT THE CARS.
 8. NOT SATISFIED- TABLE PROVIED INDICATES THAT 25 UNITS
 ARE BELOW THE MINIMUM 550 SF UNIT SIZE PERMITTED BY THE
 CODE FOR REGUALR UNITS. THOSE UNITS SHALL BE CLASSIFIED
 AS MICRO UNITS AND MUST COMPLY WITH SPECIFIC MICROUNIT
 REQUIREMENTS. PLEASE SEE SECTION 94 106 (8A) AND
 RESPOND HOW THE PROJECT IS GOING TO ADDRESS THE
 SPECIFIC REQUIREMENTS.
 9. NOT SATISFIED - TABLE PROVIDED INDICATES 8 HOTEL
 ROOMS ARE LESS THAN THE 350 SF REQUIRED FOR FULL
 SERVICE HOTELS.
 10. SATISFIED-PLEASE INDICATE THE LOCATION OF THE CAR
 LIFTS.
 11. SATISFIED- PLEASE INDICATE THE TENANT ACCESS TO THE
 BIKE STORAGE ROOM.
  
 ADDITIONAL COMMENTS FROM 1/28/19 SUBMITTAL:
 1. PLEASE CORRECT THE FAR NUMBER IN SHEET A0.0A AND
 A0.07, THE TWO NUMBERS DO NOT MATCH.
 2.PEDESTRIAN CROSSING AT THE CORNER OF 4RD AND DIXIE
 HWAY SHALL BE SPLIT INTO TWO DIRECTIONAL RAMPS.
 3. THERE ARE TWO BIKE RACKS INDICATED ON THE OFFICE
 PLAZA THAT CONFLICT WITH THE WATER FEATURE PROPOSE AND
 THE PATH OF TRAVEL FOR PEDESTRIANS. PLEASE RELOCATE.
 4.LIGHT POLES INDICATED IN SHEETL1-150 SHALL MEET THE
 DOWNTOWN CITY STANDARD FOR POLE AND FIXTURE.
 5. A LIGHTING PROTOMETRIC SHALL BE SUBMITTED FOR THE
 EXTERIOR GROUND FLOOR AREA TO CONFIRM COMPLIANCE WITH
 THE MINIMUM REQUIRED 0.6 FOOTCANDLES AT THE CURB SIDE
 ONE FOOT ABOVE GROUND.
 6. PLEASE SUBMIT DETAILS FOR THE BIKE RACKS TO CONFIRM
 SPACE PROVIDED IS ADEQUATE.
 7. PLEASE CONFIRM THE EXFILTRATION TRENCH WILL NOT
 CONFLICT WITH PROPOSED TREES ALONG DIXIE HWAY.
 8. PLEASE RECONSIDER PROPOSED GREESE TRAP UNDER HOTEL
 OUTDOOR DINING AREA.
  
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  