Plan Review Notes
Plan Review Notes For Project Z17010009
Project Number Z17010009
Review Stop STORM
Sequence Number 2
Notes
Date Text
2017-05-09 09:56:49ALL COMMENTS FROM THE FIRST STORM REVIEW WERE
 ADDRESSED.
  
 THE FOLLOWING COMMENT IS BASED ON MARCH 14, 2017
 SUBMITTAL PACKAGE:
  
 1. THE CITY COMMISSION IS CONSIDERING RAISING THE
 FREEBOARD TO TWO FEET ABOVE BASE FLOOD ELEVATION FOR
 STRUCTURES WITHIN A SPECIAL FLOOD HAZARD AREA. THE
 RESPONSE TO COMMENT 1 FROM THE INITIAL STORM REVIEW
 COMMENTS INDICATED THAT PORTIONS OF THE DEVELOPMENT
 WILL BE WITHIN AN AE ZONE WITH BASE FLOOD ELEVATION OF
 15.0' NAVD (=16.5 FT NGVD) ON THE NEW FEMA MAPS AND THE
 PROPOSED FINISHED FLOOR ELEVATION FOR THE DEVELOPMENT
 IS 18.0' NGVD, OR 1.5 FEET ABOVE THE BASE FLOOD
 ELEVATION. THIS WILL MEET THE CURRENT FREE BOARD
 CRITERIA BUT NOT THE PROPOSED FREEBOARD CRITERIA.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT