| 2017-02-03 10:01:16 | CITY OF WEST PALM BEACH |
| | PUBLIC WORKS DEPARTMENT |
| | ENGINEERING DIVISION |
| | |
| | DATE: 02/03/2017 |
| | |
| | Z17010008: 936 27TH ST. & 925 26TH ST. - MAINTENANCE |
| | BLDG. FOR R&D PAVING INDUSTRIAL SITE |
| | |
| | THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL |
| | DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION |
| | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE |
| | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT |
| | APPLICATION PROCESSES. |
| | |
| | THE FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR |
| | TO ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING |
| | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL: |
| | |
| | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL |
| | BE REQUIRED FROM THE CITY'S ENGINEERING SERVICES |
| | DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL |
| | APPLICATION FORMS CAN BE DOWNLOADED AT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | 2. PLEASE SUBMIT THE LATEST VERSION OF THE "AUTO-CALC |
| | CERTIFIED COST ESTIMATE FORM" FOR SUBMISSION TO CITY OF |
| | WEST PALM BEACH ENGINEERING SERVICES DEPARTMENT. THIS |
| | FORM CAN BE DOWNLOADED FROM THE FOLLOWING LINK: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | 3. CITY GARBAGE TRUCKS CANNOT BACK UP MORE THAN 50 |
| | FEET. SHOW/DELINEATE THE PATH OF THE GARBAGE TRUCK IN |
| | THE PLAN. CONSIDER AN ALTERNATIVE LOCATION FOR THE |
| | DUMPSTER (MUCH CLOSER TO THE ENTRANCE) SO THAT CITY?S |
| | SANITATION TRUCKS CAN EASILY ACCESS AND MANEUVER; |
| | |
| | 4. PROPOSED DUMPSTER PAD AND ENCLOSURE SHALL BE |
| | CONSISTENT WITH CITY OF WEST PALM BEACH STANDARD |
| | DETAIL. INCLUDE THE DETAIL ON THE PLANS DURING |
| | RE-SUBMITTAL. MINIMUM DIMENSION (E.G. THE GATE WIDTH |
| | MUST BE A MINIMUM OF 12.5 FEET) REQUIREMENTS FOR THE |
| | ENCLOSURE ARE LISTED IN CODE OF ORDINANCES, SECTION |
| | 94-444(B) OF THE CODE OF ORDINANCES. CITY STANDARD |
| | DETAIL GC-8 MAY BE DOWNLOADED AT: |
| | |
| | HTTP://WPB.ORG/ENGINEERING/ENGINEERING-SERVICES/ENGINEE |
| | RING-STANDARDS/ |
| | |
| | 5. IF ROLL OUT TYPE DUMPSTER IS PROPOSED, PLEASE NOTE |
| | ON THE PLANS THAT: "OWNER IS RESPONSIBLE TO ROLL OUT |
| | THE DUMPSTER OUTSIDE THE ENCLOSURE PRIOR TO CITY'S |
| | SANITATION CREW PICK UP GARBAGE". |
| | |
| | FOLLOWING ARE WATER AND SEWER COMMENTS: |
| | |
| | 6. CITY RECORD DRAWING SHOWS AN EXISTING 6-INCH DIP |
| | SANITARY SEWER LATERAL IS SERVING THE PROPERTY |
| | (CLEANOUT NEAR THE PROPERTY LINE). IT IS RECOMMENDED TO |
| | UTILIZE THE EXISTING LATERAL/CONNECTION; |
| | |
| | 7. CITY RECORD DRAWING SHOWS AN EXISTING 1-INCH |
| | WATERLINE AND AN EXISTING WATER METER IS SERVING THE |
| | PROPERTY. IT IS RECOMMENDED TO UTILIZE THE EXISTING |
| | SERVICE CONNECTION; |
| | |
| | 8. ANY WATERLINE THAT HAS NOT BEEN USED FOR A WHILE |
| | SHALL REQUIRE BAC-T TESTING PRIOR TO CONNECTION FOR NEW |
| | SERVICE; |
| | |
| | 9. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE |
| | CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE |
| | DETAILS SHEET. CONTACT THE ENGINEERING SERVICES |
| | DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD |
| | FORMAT. CITY'S STANDARD DETAILS (IN PDF FILE FORMAT) |
| | CAN BE DOWNLOADED FROM THE FOLLOWING SITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | 10. ANY NEW/PROPOSED WATER METER AND BACKFLOW PREVENTER |
| | SHALL BE INSTALLED PER THE CITY'S STANDARD DETAILS. |
| | WATER METER SHOULD BE INSIDE AN 'UTILITY EASEMENT' JUST |
| | INSIDE THE PROPERTY NEAR THE RIGHT-OF-WAY AND |
| | ACCESSIBLE; |
| | |
| | 11. PERFORM SOFTDIGS DATA AND PROVIDE UTILITY CROSSING |
| | INFORMATION. SHOW CONFLICT INFORMATION (BOTTOM AND TOP |
| | OF CROSSING PIPES) AT THE CONFLICT POINTS OF ALL WATER, |
| | STORM AND SANITARY SEWER PIPES AS WELL AS OTHER |
| | FRANCHISE UTILITIES; |
| | |
| | 12. PAVEMENT RESTORATION WILL BE REQUIRED AND SHALL BE |
| | PER THE CITY STANDARD DETAILS (GC-9 AND P-4) IF |
| | PROPOSED WATER AND SANITARY SEWER CONNECTION WORK IS |
| | PERFORMED WITHIN THE RIGHT-OF-WAY; |
| | |
| | 13. EXISTING WATER SERVICE CONNECTIONS/WATER METERS |
| | SERVING THE PROPERTY, IF NOT USED, ARE TO BE CUT AND |
| | CAPPED AT THE MAIN. DE-ACTIVATED/INACTIVE PIPELINES |
| | LARGER THAN 2-INCH DIAMETER WILL BE REMOVED. PLEASE |
| | LABEL PIPE SIZE AND MATERIAL AND ADD NOTES TO THE |
| | UTILITY PLANS ACCORDINGLY; |
| | |
| | 14. PLEASE NOTE THAT: AS OF DECEMBER 20, 2015 THE CITY |
| | OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL HAS |
| | BEEN REVISED, MAKING KNOWN THAT "ALL BACKFLOW DEVICES |
| | MUST BE LEAD FREE." FOR MORE INFORMATION REFER TO THE |
| | LINK BELOW: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI |
| | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
| | |
| | 15. LANDSCAPE PLAN SHALL SHOW LOCATIONS OF ALL WATER |
| | METERS, VALVES, CLEAN-OUTS, LIGHT POLES, ETC. ROOT |
| | BARRIERS MAY BE REQUIRED WHERE PLANTINGS ARE NEAR |
| | UNDERGROUND STORMWATER, SANITARY, OR POTABLE WATER |
| | LINES. |
| | |
| | MOSTAQUE KHAN, P.E. |