Plan Review Notes
Plan Review Notes For Project Z17010007
Project Number Z17010007
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-02-06 14:19:38THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 4. THE CONSTRUCTION OF ANY BUILDING SHALL COMPLY WITH
 REQUIREMENTS OF THE 5TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE, INCLUDING NFPA 1 & 101, AND ALL
 ASSOCIATED FIRE CODES.
  
 5. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT AN
 APPLICABLE FIRE EXTINGUISHER IS LOCATED WITHIN THE
 GUARDHOUSE.
  
 6. NO INDICATIONS OF FIRE HYDRANT LOCATIONS COULD BE
 DETERMINED FROM THE SUBMITTAL. ALL EXISTING AND NEW
 FIRE HYDRANTS PLANNED FOR THIS DEVELOPMENT SHALL BE
 CLEARLY INDICATED AND IDENTIFIED ON THE PLAN AND
 CLOSELY COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 7. IT IS HIGHLY RECOMMENDED FOR ANY ACCESS GATES THAT
 THEY BE PROVIDED WITH KNOX KEY SWITCHES FOR 24 HOUR
 EMERGENCY ACCESS. BOTH GATES SHALL OPEN ON ACTIVATION
 OF THE KEY SWITCH OR EXITING WHEN ACTIVATING ANY
 AUTOMATIC OPEN DEVICE. THIS PROVIDES FOR ADAQUATE
 CLEARENCE DISTANCES FOR WIDE EMERGENCY APPARATUS.
  
 8. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 9. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS
 AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  