Plan Review Notes
Plan Review Notes For Project Z16120027
Project Number Z16120027
Review Stop STORM
Sequence Number 1
Notes
Date Text
2017-01-11 10:33:35THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT
 HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?.
 PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS
 WILL NOT IMPACT THE PROPOSED PROJECT.
  
 2. THE CITY COMMISSION RECENTLY PASSED A RESOLUTION
 INCREASING THE FREEBOARD REQUIREMENT TO ONE FOOT ABOVE
 BASE FLOOD ELEVATION FOR STRUCTURES IN A SPECIAL FLOOD
 HAZARD AREA.
  
 3. IDENTIFY THE ENTITY RESPONSIBLE TO MAINTAIN THE
 ONSITE DRAINAGE SYSTEMS.
  
 4. INDICATE WHETHER THE DRAINAGE SYSTEM (MANHOLES AND
 PIPES) IN THE LWDD CANAL R/W HAS BEEN CONSTRUCTED. IF
 SO, PLEASE SUBMIT A COPY OF THE AS-BUILT DRAWINGS. IF
 NOT, PROVIDE THE DESIGN INFORMATION FOR THE SYSTEM.
  
 5. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE ENGINEERING CALCULATIONS SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER FOR THE
 MINIMUM REQUIRED STORM RUNOFF WATER QUALITY TREATMENT
 AND PEAK FLOOD STAGES FOR 5-YEAR 1-DAY, 25-YEAR 3-DAY
 AND 100-YEAR 3-DAY DESIGN STORMS PER SFWMD CRITERIA.
  
 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION FOR
 THIS PROPOSED DEVELOPMENT. NOTE SFWMD PERMIT NO.
 50-11023-P ASSUMED THE SITE WOULD BE GRADED NO HIGHER
 THAN ELEVATION 15 NGVD AND DID NOT INCLUDE IMPERVIOUS
 AREA (OTHER THAN THE ENTRANCE ROAD FROM OKEECHOBEE BLVD
 TO THE DEVELOPMENT) WITHIN THE LWDD LATERAL CANAL L-1
 R/W. PRELIMINARY ENGINEERING PLAN SHEET 2 OF 5 SHOWS
 MINIMUM ELEVATION OF 16.15 AT CB C1 AND PART OF THE
 PARKING LOT ON THE LWDD CANAL R/W.
  
 4. PROVIDE A COPY OF THE LWDD PERMIT(S) FOR THIS
 PROJECT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  