Plan Review Notes
Plan Review Notes For Project Z16110016
Project Number Z16110016
Review Stop STORM
Sequence Number 2
Notes
Date Text
2017-01-19 08:35:11THESE COMMENTS ARE FROM THE REVIEW OF THE THE JANUARY
 11, 2017 SUBMITTAL PACKAGE:
  
 1. STORMWATER QUALITY TREATMENT IS NEEDED FOR THE
 PARKING LOT SOUTH OF THE HOTEL.
  
 2. THE PROPOSED, RELOCATED 18" SANITARY SEWER MAY BE IN
 CONFLICT WITH THE EXISTING 36" RCP STORM PIPE.
  
 3. INDICATE MILL AND OVERLAY LIMITS WHERE UTILITES ARE
 BEING CONSTRUCTED IN THE ROAD PER CITY STANDARDS.
  
 4. RECOMMEND CONDUCTING A CONDITION ASSESSMENT OF THE
 EXISTING CLAY STORM PIPES WITHIN THE SITE.
  
 5. SURVEY AND ENGINEERING PLANS ARE USING DIFFERENT
 VERTICAL DATUMS. THE CURRENT CITY DATUM IS NATIONAL
 GEODETIC VERTICAL DATUM OF 1929 (NGVD1929). THE NORTH
 AMERICAN VERTICAL DATUM OF 1988 (NAVD1988) MAY BE USED
 FOR THIS SITE PROVIDED A CONVERSION FACTOR BETWEEN
 NAVD1988 AND NGVD1929 IS PROVIDED. THE VERTICAL DATUM
 SHOULD BE CONSISTENT ACROSS ALL PLANS/SURVEYS AND
 LABELED ON THE SHEETS WHERE ELEVATION INFORMATION IS
 PROVIDED.
  
 TRACY L. WARD, P.E.
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120
  
  