| Plan Review Notes For Project Z16110016 |
| Project Number |
Z16110016 |
|
| Review Stop |
STORM |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-19 08:35:11 | THESE COMMENTS ARE FROM THE REVIEW OF THE THE JANUARY | | | 11, 2017 SUBMITTAL PACKAGE: | | | | | | 1. STORMWATER QUALITY TREATMENT IS NEEDED FOR THE | | | PARKING LOT SOUTH OF THE HOTEL. | | | | | | 2. THE PROPOSED, RELOCATED 18" SANITARY SEWER MAY BE IN | | | CONFLICT WITH THE EXISTING 36" RCP STORM PIPE. | | | | | | 3. INDICATE MILL AND OVERLAY LIMITS WHERE UTILITES ARE | | | BEING CONSTRUCTED IN THE ROAD PER CITY STANDARDS. | | | | | | 4. RECOMMEND CONDUCTING A CONDITION ASSESSMENT OF THE | | | EXISTING CLAY STORM PIPES WITHIN THE SITE. | | | | | | 5. SURVEY AND ENGINEERING PLANS ARE USING DIFFERENT | | | VERTICAL DATUMS. THE CURRENT CITY DATUM IS NATIONAL | | | GEODETIC VERTICAL DATUM OF 1929 (NGVD1929). THE NORTH | | | AMERICAN VERTICAL DATUM OF 1988 (NAVD1988) MAY BE USED | | | FOR THIS SITE PROVIDED A CONVERSION FACTOR BETWEEN | | | NAVD1988 AND NGVD1929 IS PROVIDED. THE VERTICAL DATUM | | | SHOULD BE CONSISTENT ACROSS ALL PLANS/SURVEYS AND | | | LABELED ON THE SHEETS WHERE ELEVATION INFORMATION IS | | | PROVIDED. | | | | | | TRACY L. WARD, P.E. | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 | | | | | | |
| |