Plan Review Notes
Plan Review Notes For Project Z16110015
Project Number Z16110015
Review Stop STORM
Sequence Number 2
Notes
Date Text
2017-03-27 11:06:56COMMENTS ON MARCH 23, 2017 REVIEW PACKAGE:
  
 1. LANDSCAPE PLAN SHOWS TREES PROPOSED OVER OR NEAR THE
 ON-SITE DRAINAGE SYSTEMS INCLUDING ALONG THE SOUTH AND
 WEST PROPERTY LINES AND ALONG THE ONSITE EXFILTRATION
 TRENCH SOUTH OF FLAMINGO DRIVE. HOW WILL THE DRAINAGE
 SYSTEM BE PROTECTED FROM ROOT INTRUSION AND FUTURE
 MAINTENANCE NEEDS OF THE DRAINAGE SYSTEMS?
  
 2. PHASE II CONCEPTUAL PLAN SHOWS EXISTING DRAINAGE
 (EXDN) UNDER THE PROPOSED BUILDING. IS THIS DRAINAGE TO
 REMAIN?
  
 3. LABEL THE CIRCULAR SYMBOL SHOWN TO THE WEST OF THE
 RELOCATED CONTROL STRUCTURE ON THE CONCEPTUAL PLAN. IS
 THIS A STORM MANHOLE?
  
 4. WHAT ARE THE LONG NARROW HATCHING AREAS ON SOUTH AND
 EAST SIDES OF PROPOSED BUILDING SHOWN ON THE CONCEPTUAL
 PLAN SHEET?
  
 5. THERE APPEARS TO BE AN EXISTING WATER MAIN ADJACENT
 TO THE STORM PIPE BETWEEN THE RELOCATED CONTROL
 STRUCTURE AND MANHOLE IN BISCAYNE DRIVE. THERE NEEDS TO
 BE A MINIMUM FIVE FEET HORIZONTAL CLEARANCE BETWEEN THE
 WATER AND STORM PIPE.
  
 TRACY L. WARD, P.E.
 SENIOR STORMNWATER ENGINEER
 [email protected]
 561-494-1120
  