Plan Review Notes
Plan Review Notes For Project Z16110014
Project Number Z16110014
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2016-12-11 20:38:21CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
 ENGINEERING DIVISION
  
 DATE: 12/12/2016
  
 Z16110014: 1560 PALM BEACH LAKES BLVD. - HOME DEPOT CPD
  
 THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR
 TO ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL:
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC
 WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION FORMS CAN BE DOWNLOADED AT:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC
 CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT. THIS FORM CAN
 BE DOWNLOADED FROM THE FOLLOWING LINK:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 3. SOLID WASTE YARDAGE CALCULATION WILL NEED TO BE
 SUBMITTED AS PART OF THE FINAL DESIGN TO VERIFY THAT
 THE DESIGN INCLUDES APPROPRIATE NUMBER AND SIZE OF
 DUMPSTERS/GARBAGE RECEPTACLES. PLEASE SHOW ON THE PLAN
 IF A COMPACTOR IS PROPOSED TO REDUCE THE YARDAGE OF
 WASTE THAT WILL NEED TO BE COLLECTED;
  
 4. PROVIDE STATEMENT OR DOCUMENTATION THAT THE PROPOSED
 SANITATION FACILITY/DUMPSTER CAN BE PLACED AND ACCESSED
 AT THE SPECIFIED LOCATION AS SHOWN ON THE PLANS;
  
 5. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING
 THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS THE
 PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. THE TRASH
 DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY
 SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER
 PER SECTION 74-35(A)(5) OF THE CODE OF ORDINANCES. IF A
 ROLL?OFF COMPACTOR IS PROPOSED, PLEASE PROVIDE A LETTER
 FROM THE PRIVATE PROVIDER VERIFYING THAT THEY CAN
 PROVIDE SERVICE WITH THE CONFIGURATION SHOWN ON THE
 PLANS;
  
 6. PLEASE INCLUDE THE CITY OF WEST PALM BEACH STANDARD
 DETAIL FOR THE DUMPSTER ENCLOSURE ON THE PLANS. MINIMUM
 DIMENSIONAL (E.G. THE GATE WIDTH MUST BE A MINIMUM OF
 12.5 FEET) REQUIREMENTS FOR THE ENCLOSURE ARE LISTED IN
 CODE OF ORDINANCES, SECTION 94-444(B) OF THE CODE OF
 ORDINANCES. CITY STANDARD DETAIL GC-8 MAY BE DOWNLOADED
 AT:
  
 HTTP://WPB.ORG/ENGINEERING/ENGINEERING-SERVICES/ENGINEE
 RING-STANDARDS/
  
 7. IF ROLL OUT TYPE DUMPSTER IS PROPOSED, PLEASE NOTE
 ON THE PLANS THAT: 'OWNER IS RESPONSIBLE TO ROLL OUT
 THE DUMPSTER OUTSIDE THE ENCLOSURE PRIOR TO CITY'S
 SANITATION CREW PICK UP GARBAGE'.
  
 THE FOLLOWING WATER AND SEWER COMMENTS:
  
 8. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND
 SANITARY SEWER CALCULATION (AVERAGE AND PEAK WITH
 PEAKING FACTOR). SUBMIT CALCULATIONS TO VALIDATE METER
 SIZE SELECTION. SHOW THESE CALCULATIONS ON THE UTILITY
 PLAN SHEET AS WELL;
  
 9. FIRE HYDRANT FLOW TEST DATA FROM EXISTING FIRE
 HYDRANT WILL BE REQUIRED PART OF THE PLAN SUBMITTAL;
  
 10. PROPOSED WATER CONNECTION TO THE RESTAURANT 'A-2'
 IS SHOWN ON THE UTILITY PLAN TO BE FROM A PRIVATE FIRE
 LINE. WATER SERVICE IS AVAILABLE FROM PALM BEACH LAKES
 BLVD;
  
 11. PROPOSED WATER CONNECTION TO THE RETAIL SPACE 'A-1'
 IS SHOWN ON THE UTILITY PLAN TO BE FROM A WATERLINE
 THAT IS DEDICATED TO THE ADJACENT BUSINESS. WATER
 SERVICE IS AVAILABLE FROM PALM BEACH LAKES BLVD;
  
 12. PLEASE NOTE ON THE PLAN THAT ?WATERLINE THAT HAS
 NOT BEEN USED FOR A WHILE SHALL REQUIRE BAC-T TESTING
 PRIOR TO CONNECTION FOR NEW SERVICE?;
  
 13. SHOW ON THE PLANS LOCATION OF FIRE DEPARTMENT
 CONNECTIONS (FDC). PROPOSED FIRE DEPARTMENT CONNECTION
 SHALL BE WITHIN 150 FEET OF A FIRE HYDRANT AND SHALL BE
 WITHIN AN EASEMENT WITHIN THE PROPERTY;
  
 14. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE
 CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE
 DETAILS SHEET. CONTACT THE ENGINEERING SERVICES
 DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD
 FORMAT. CITY'S STANDARD DETAILS (IN PDF FILE FORMAT)
 CAN BE DOWNLOADED FROM THE FOLLOWING SITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 15. PLACEMENT OF THE PROPOSED METER, BACKFLOW
 PREVENTER, DCDA ETC. SHALL BE INSTALLED PER THE CITY'S
 STANDARD DETAILS. WATER METER SHOULD BE INSIDE AN
 'UTILITY EASEMENT' JUST INSIDE THE PROPERTY NEAR THE
 RIGHT-OF-WAY AND ACCESSIBLE;
  
 16. SHOW CONFLICT INFORMATION (BOTTOM AND TOP OF
 CROSSING PIPES) AT THE CONFLICT POINTS OF ALL WATER,
 STORM AND SANITARY SEWER PIPES AS WELL AS OTHER
 FRANCHISE UTILITIES;
  
 17. THERE IS AN EXISTING SANITARY SEWER LATERAL STUB
 (LOCATED JUST NORTH OF THE EXISTING SANITARY MANHOLE)
 AVAILABLE NEAR THE NORTHWEST PROPERTY CORNER. IS THERE
 A REASON WHY PROPOSED SANITARY SEWER SERVICE CONNECTION
 IS NOT UTILIZING THIS EXISTING SUB?
  
 18. SHOW DIRECTION OF FLOW FOR THE EXISTING SANITARY
 SEWER. INCLUDE A PROFILE FOR PROPOSED SERVICE LATERAL
 WITH GROUND ELEVATIONS ABOVE THE PIPE;
  
 19. CCTV RECORD (VIDEO AND TV LOG) OF THE EXISTING
 SANITARY SEWER (FULL LENGTH FROM MH TO MH) AND NEW
 SANITARY SEWER LATERAL WILL BE REQUIRED AS PART OF THE
 PROJECT CLOSE-OUT SUBMITTALS;
  
 20. PAVEMENT RESTORATION WILL BE REQUIRED FOR PROPOSED
 WATER AND SEWER CONNECTION IF PERFORMED WITHIN CITY'S
 RIGHT-OF-WAY AND SHALL BE SHOWN ON THE UTILITY PLAN.
 REFER TO THE CITY'S LATEST STANDARD DETAIL FOR THE
 PAVEMENT RESTORATION GUIDELINES;
  
 21. EXISTING WATER SERVICE CONNECTIONS/WATER METERS
 SERVING THE PROPERTY, IF NOT USED, ARE TO BE CUT AND
 CAPPED AT THE MAIN. DE-ACTIVATED/INACTIVE PIPELINES
 LARGER THAN 2" DIAMETER WILL BE REMOVED. PLEASE LABEL
 PIPE SIZE AND MATERIAL AND ADD NOTES TO THE UTILITY
 PLANS ACCORDINGLY;
  
 22. PLEASE NOTE THAT: AS OF DECEMBER 20, 2015 THE CITY
 OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL HAS
 BEEN REVISED, MAKING KNOWN THAT "ALL BACKFLOW DEVICES
 MUST BE LEAD FREE." FOR MORE INFORMATION REFER TO THE
 LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 23. LANDSCAPE PLAN SHALL SHOW LOCATIONS OF ALL WATER
 METERS, VALVES, CLEAN-OUTS, LIGHT POLES, ETC. ROOT
 BARRIERS MAY BE REQUIRED WHERE PLANTINGS ARE NEAR
 UNDERGROUND STORMWATER, SANITARY, OR POTABLE WATER
 LINES.
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1024 (OFFICE)
  
  