| 2016-10-31 11:52:44 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE |
| | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A |
| | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED |
| | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN |
| | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY |
| | MONITORED FOR THE POTENTIAL REQUIREMENT OF FIRE |
| | SPRINKLER PROTECTION. |
| | |
| | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY |
| | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING |
| | ALL CONSTRUCTION ACTIVITIES. |
| | |
| | 3. THE BUILDINGS ADDRESSES SHALL BE CLEARLY VISIBLE |
| | FROM ALL ACCESS ROADWAYS, INCLUDING DURING |
| | CONSTRUCTION. ADDRESS NUMBERS SHALL CONTRAST WITH THEIR |
| | BACKGROUND AND SHALL NOT BE LESS THAN SIX (6) INCHES IN |
| | HEIGHT WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. |
| | |
| | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE |
| | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE |
| | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. |
| | |
| | 5. THE CONSTRUCTION OF THE BUILDINGS SHALL COMPLY WITH |
| | THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, |
| | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. |
| | |
| | 6. A NFPA 13 COMPLIANT FIRE SPRINKLER SYSTEM AND NFPA |
| | 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR |
| | THESE STRUCTURES. TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES THREE LEVELS OR THIRTY FEET |
| | WHILE BEING CONSTRUCTED. |
| | |
| | SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED, |
| | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU |
| | PRIOR TO ANY INSTALLATION. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | |
| | 7. A NFPA 72 COMPLIANT MONITORED FIRE ALARM SYSTEM IS |
| | REQUIRED FOR THESE STRUCTURES. |
| | |
| | SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED, |
| | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU |
| | PRIOR TO ANY INSTALLATION. |
| | |
| | |
| | 8. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7 |
| | KEYWAY SYSTEM. |
| | |
| | ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER'S |
| | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA |
| | B44, SAFETY CODE FOR ELEVATORS. |
| | |
| | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN |
| | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL |
| | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET |
| | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER |
| | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN |
| | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE |
| | IN THE HORIZONTAL POSITION. |
| | |
| | |
| | 9. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL |
| | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, |
| | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A |
| | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE |
| | SAFETY FEATURES AND EQUIPMENT. |
| | |
| | |
| | 10. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS |
| | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED |
| | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF |
| | FIRE PREVENTION. |
| | |
| | THE PROPOSED FIRE HYDRANT LOCATIONS AND FDC'S ARE ON |
| | OPPOSITE SIDE OF THE TRAVEL LANE. FOR FIRE OPERATIONAL |
| | PURPOSES PLEASE RELOCATE THEM TO THE SAME SIDE OF THE |
| | TRAVEL LANE. |
| | |
| | THE PROPOSED FDC'S ARE INDICATED ON PARKING ISLANDS |
| | WHERE THEY CAN BE DAMAGED BY VEHICLE TRAFFIC. IT IS |
| | STRONGLY RECOMMENDED THAT THEY BE MOVED TO INTERIOR |
| | LOCATIONS BEYOND THE SIDEWALKS. |
| | |
| | |
| | 11. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS |
| | BUILDING. |
| | |
| | ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, |
| | PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. |
| | |
| | ACTIVATION OF THE KNOX KEY SWITCH AT THE ENTRY POINTS |
| | SHALL OPEN BOTH GATES. |
| | |
| | |
| | 12. THE CANOPY PROTECTING THE GATE ENTRY PAD PROJECTS |
| | INTO THE FIRE LANE |
| | |
| | FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED |
| | VERTICAL CLEARANCE OF NOT LESS THAN 13 FT 6 IN. (4.1 |
| | M). |
| | |
| | VERTICAL CLEARANCE SHALL BE PERMITTED TO BE REDUCED, |
| | PROVIDED SUCH REDUCTION DOES NOT IMPAIR ACCESS BY FIRE |
| | APPARATUS, AND APPROVED SIGNS ARE INSTALLED AND |
| | MAINTAINED INDICATING THE ESTABLISHED VERTICAL |
| | CLEARANCE WHEN APPROVED. |
| | |
| | PLEASE PROVIDE DETAILS OF HOW THE LOW CLEARENCE HEIGHT |
| | WILL BE INDICATED AND FIRE APPARATUS APPROACH WILL BE |
| | PROTECTED. |
| | |
| | |
| | 13. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT |
| | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| | |
| | |
| | 14. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING |
| | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| |