| Plan Review Notes For Project Z16080012 |
| Project Number |
Z16080012 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-06 16:52:01 | THE PREVIOUS COMMNETS FROM THE BUREAU OF FIRE | | | PREVENTION WERE ADDRESSED UNDER COMMNET REVIEW. | | | | | | THE FOLLOWING ADDITIONAL COMMENTS WERE SUBMITTED BY | | | PETER LEDUC, FIRE MARSHAL, BUREAU OF FIRE PREVENTION, | | | WEST PALM BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | | | | | | | 1) THE LOCATION OF THE FIRE HYDRANT AND FDC ON ARKONA | | | CT WOULD BE BETTER LOCATED CLOSER TO THE ENTRANCE RAMP | | | AND ACCESS TO THE FIRE COMMAND ROOM AREA. | | | | | | | | | | | | 2) THE LOCATION OF THE FIRE PUMP ROOM WOULD BE BETTER | | | LOCATED ON A OUTSIDE WALL WITH EXTERIOR ACCESS AND NEXT | | | TO THE FIRE COMMAND ROOM FOR EFFECTIVE AND EFFICIENT | | | ACCESS. | | | | | | | | | | | | 3) PLEASE CONFIRM THAT THERE IS ACCESS TO THE BUILDING | | | FROM FLAGER DR AT THE LOCATION OF THE FDC AND FIRE | | | HYDRANT. | | | | | | | | | | | | 4) PLEASE ENSURE THERE IS CODE COMPLIANT WALL | | | SEPARATION/RATING SURROUNDING THE BOLIER ROOM MEETING | | | NFPA 85 WERE APPLICABLE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | |
| |
Print |
|