| 2017-01-10 09:33:05 | CITY OF WEST PALM BEACH |
| | ENGINEERING SERVICES DEPARTMENT |
| | |
| | PROJECT NAME: 1515 S. FLAGLER DR. - THE MODERN - |
| | Z16080012 |
| | DATE: JANUARY 10, 2017 |
| | |
| | STATUS: PASSED WITH PROVISO (STATED BELOW): |
| | |
| | AFTER A REVIEWING THE REVISED PLANS AND THE RESPONSES |
| | TO THE PPRC COMMENTS (RECEIVED ON 12/21/2016), IT |
| | APPEARS THAT SOME OF THE PREVIOUS COMMENTS HAVE BEEN |
| | ACKNOWLEDGED. HOWEVER, THESE ACKNOWLEDGED COMMENTS |
| | ALONG WITH THE FOLLOWING ITEMS ARE EXPECTED TO BE |
| | ADDRESSED DURING 'ENGINEERING DEVELOPMENT APPLICATION' |
| | PHASE PRIOR TO ISSUANCE OF CONSTRUCTION AUTHORIZATION |
| | INCLUDING BUILDING PERMITS AND ENGINEERING DEVELOPMENT |
| | APPROVAL: |
| | |
| | 5. REVISED 'UTILITY PLAN - C6.00' SHOWS A WATER |
| | CONNECTION COMING INSIDE THE PROPERTY FROM SOUTH |
| | FLAGLER DRIVE (NEAR THE THREE EXISTING WATER VALVES AND |
| | JUST NORTH OF THE PROPOSED 'POINT OF WATER SERVICE'). |
| | IT NEEDS TO BE CUT AND CAPPED AND CALLED OUT SO IN THE |
| | PLAN, IF NOT USED FOR THE DEVELOPMENT; |
| | 6. SIGNED & SEALED ENGINEER/MEP WATER AND SEWER DEMAND |
| | CALCULATIONS (AVERAGE AND PEAK) FOR METER SIZING |
| | SELECTION AND SERVICE SIZING NEED TO BE SUBMITTED PRIOR |
| | TO 'BUILDING PERMIT'. ALSO NEEDED IS CALCULATION FOR |
| | FIRE FLOW DEMAND; |
| | 7. REVISED 'UTILITY PLAN' DOES NOT CONTAIN FIRE HYDRANT |
| | FLOW TEST DATA FROM EXISTING FIRE HYDRANT USED FOR |
| | DESIGN. WAS IT SUBMITTED IN A SEPARATE DOCUMENT? PLEASE |
| | SUBMIT THE INFORMATION WITH THE DETAIL ENGINEEING PLANS |
| | DURING SUBMISSION OF 'ENGINEER DEVELOPMENT APPLICATION' |
| | PHASE. |
| | 10. PREVIOUS COMMENT OF: 'CITY'S RECORD INFORMATION |
| | SHOWS THAT FROM AN EXISTING SAN MH AT THE OLIVE AVENUE |
| | AND CRANENEST WAY INTERSECTION, THERE IS AN 8-INCH |
| | SANITARY SEWER THAT RUNS EAST FOR APPROXIMATELY 320 LF |
| | AND TERMINATE ON THE SUBJECT PROPERTY. THERE IS NEED TO |
| | TELEVISE THIS MAIN AND CALL OUT THE PIPE SECTION WITHIN |
| | THE R/W TO BE REMOVED IF NOT IN USE'. SUBMITTED SURVEY |
| | AND REVISED 'UTILITY PLAN' DOES NOT SHOW THIS LINE. IT |
| | HAS BEEN 'ACKNOWLEDGED' IN THE RESPONSE BUT NO PROPOSED |
| | PLAN IS SHOWN ON THE PLAN. PLEASE ADDRESS THIS COMMENT |
| | AS ADVISED; |
| | |
| | THE FOLLOWING NEW COMMENT MUST BE ALSO ADDRESSED PRIOR |
| | TO ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING |
| | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL: |
| | |
| | 12. EXISTING MANHOLE AT THE INTERSECTION OF SOUTH |
| | FLAGLER DRIVE AND ARKONA CT. WHERE THE PROPOSED |
| | SANITARY SEWER IS CONNECTED SHALL BE REHABILITATED PER |
| | CITY STANDARD; |
| | 13. AUTOTURN ANALYSIS IS NOT INCLUDED IN THE PLANS; |
| | 14. PAVEMENT RESTORATION SHOWN ON THE REVISED 'UTILITY |
| | PLAN - C6.00' SHALL BE PER THE DETAIL P-4 I.E. 'FULL |
| | LANE WIDTH OF TRAVEL LANE(S) ENCROACHED BY THE TRENCH |
| | AREA, INCLUDING A TRANSITION AREA OF 50 FEET ON EACH |
| | SIDE OF THE TRENCH'. PLEASE REVISE THE PAVEMENT |
| | RESTORATION HATCH AREA ACCORDINGLY FOR ALL WATER AND |
| | SEWER CONNECTION WORK; |
| | 15. INCLUDE THE CITY'S STANDARD DETAIL FOR PARKING |
| | STALL STRIPING DETAIL; |
| | |
| | MOSTAQUE KHAN, P.E. |
| | LAND DEVELOPMENT ENGINEER |
| | [email protected] |
| | 561-494-1124 (OFFICE) |
| | |
| |