| Date |
Text |
| 2017-01-11 11:46:12 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. THE PROPOSED BUILDING WILL BE IN FLOOD ZONE. |
| | CORRECTION OF THE FOLLOWING TYPOGRAPICAL ERROR WILL BE |
| | CHECKED WHEN SUBMITTED FOR PERMIT. SHEET A114 STATES |
| | THE ELEVATION OF THE MECHANICAL ROOMS AS 6'-9" NGVD. |
| | THAT APPEARS TO BE A TYPOGRAPHICAL ERROR BECAUSE, |
| | ACCORDING TO THE COMMENT RESPONSE NARRATIVE, THIS |
| | SHOULD BE 9'-6" NGVD. THE ELEVATION OF THE FIRST FLOOR |
| | OF THE BUILDING AND ALL ASSOCIATED MECHANICAL EQUIPMENT |
| | (CHILLERS, GENERATORS ETC.) SHALL BE 12 INCHES |
| | (FREEBOARD) ABOVE THE BASE FLOOD ELEVATION. |
| | |
| | 3. SHEET A114, GROUND FLOOR PLAN, DOES NOT SHOW A SAFE |
| | PEDESTRIAN ROUTE FROM THE NORTH-WEST OR THE SOUTH-WEST |
| | STAIR TO THE SIDEWALK. |
| | |
| | 4. SHEET A115, LEVEL 2 PLAN, THE EXIT DOOR FROM THE |
| | SOUTH-WEST SHOULD SWING OUTWARD. |
| | |
| | 5. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL CLEARLY |
| | SHOW THE ACCESSIBLE WALKWAY FROM THE SIDEWALK TO THE |
| | BUILDING EMTRANCE. IF THAT IS TO BE BY MEANS OF THE |
| | MEANDERING WALKWAY, SHOWN ON SHEET A115, LEVEL 2 PLAN, |
| | LEADING FROM ARKONA COURT UP THE LANDSCAPE BERM TO THE |
| | ARRIVAL COURT AT THE NORTH-WEST CORNER OF THE BUILDING, |
| | IT SHALL BE CLEARLY SHOWN TO HAVE A SLOPE OF 1 IN 20 OR |
| | BETTER. ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE |
| | GREATER THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL |
| | COMPLY WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 6. SHEET A122, LEVEL 25. THERE APPEARS TO BE A DRAFTING |
| | ERROR. WHEN SUBMITTED FOR PERMIT THE CORRIDOR LEADING |
| | TO THE EAST STAIR SHALL BE CLEARLY SHOWN WITHOUT A WALL |
| | ACROSS THE CORRIDOR. AS CURRENTLY SHOWN, THE PENTHOUSE |
| | APPEARS TO HAVE ACCESS TO ONLY THE WEST STAIR. THERE IS |
| | CURRENTLY NO EXIT PATH SHOWN TO ACCESS THE EAST STAIR |
| | BECAUSE A WALL IS SHOWN OPPOSITE THE ELEVATOR 1 LANDING |
| | DOOR. A MINIMUM OF TWO SEPARATE EXITS IS REQUIRED. |
| | |
| | 7. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES |
| | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO |
| | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL |
| | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE |
| | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED |
| | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR |
| | OTHER APPROVED METHODS. |
| | |
| | 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |