| 2016-09-14 11:01:08 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, |
| | COMMENTS: |
| | |
| | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE |
| | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH |
| | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE |
| | ADDRESSED FOR PERMITTING. |
| | |
| | 2. THE PROPOSED BUILDING WILL BE IN FLOOD ZONE. THE |
| | ELEVATION OF THE FIRST FLOOR OF THE BUILDING AND ALL |
| | ASSOCIATED MECHANICAL EQUIPMENT (CHILLERS, GENERATORS |
| | ETC.) SHALL BE 12 INCHES (FREEBOARD) ABOVE THE BASE |
| | FLOOD ELEVATION. |
| | |
| | 3. SIX ACCESSIBLE PARKING SPACES ARE SHOWN ON SHEET |
| | A113, GROUND FLOOR PLAN, BUT FOUR OF THEM DO NOT HAVE |
| | ACCESSIBLE ACCESS AISLE. ACCESSIBLE PARKING SPACE |
| | ACCESS AISLES SHALL BE LOCATED SO THAT THE USER IS NOT |
| | COMPELLED TO WALK OR WHEEL BEHIND ANOTHER PARKED |
| | VEHICLE OR IN THE TRAVEL LANE. THE ACCESS AISLES SHALL |
| | ALSO COMPLY WITH THE OTHER PROVISIONS OF SECTION OF |
| | 502.3 OF FLORIDA ACCESSIBILITY CODE. |
| | |
| | 4. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, |
| | ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE) IN A |
| | PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND |
| | DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA |
| | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 |
| | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE) |
| | |
| | 5. SHEET A114, LEVEL 2 ? AMENITIES PLAN. NO EXIT DOOR |
| | IS SHOWN TO ACCESS THE WEST STAIR. |
| | |
| | 6. SHEET A115, LEVEL 3. INDOOR AMENITIES SPACE IS |
| | LIKELY TO BE AN ASSEMBLY OCCUPANCY, BUT ONLY ONE EXIT |
| | IS SHOWN. THE ONLY ACCESS TO THE WEST STAIR TAKES |
| | OCCUPANTS PAST THE EAST STAIR, SO ONE FIRE EVENT COULD |
| | ENDER BOTH STAIRS UNAVAILABLE. A MINIMUM OF TWO |
| | SEPARATE EXITS IS REQUIRED. |
| | |
| | 7. SHEET A116, LEVEL 4. WHAT IS THE PURPOSE OF THE |
| | GREAT LOUNGE? IS THAT SPACE AN ASSEMBLY OCCUPANCY? ONLY |
| | ONE EXIT IS SHOWN, BECAUSE THE ONLY ACCESS TO THE WEST |
| | STAIR TAKES OCCUPANTS PAST THE EAST STAIR, SO ONE FIRE |
| | EVENT COULD ENDER BOTH STAIRS UNAVAILABLE. A MINIMUM OF |
| | TWO SEPARATE EXITS IS REQUIRED IF IT IS AN ASSEMBLY |
| | OCCUPANCY. |
| | |
| | 8. SHEET A121, LEVEL 26. THE PENTHOUSE APPEARS TO HAVE |
| | ACCESS TO ONLY THE WEST STAIR. THERE IS NO EXIT PATH |
| | SHOWN TO ACCESS THE EAST STAIR. A MINIMUM OF TWO |
| | SEPARATE EXITS IS REQUIRED. |
| | |
| | 9. SHEET A122, LEVEL 27. THE PENTHOUSE APPEARS TO HAVE |
| | ACCESS TO ONLY THE WEST STAIR. THERE IS NO EXIT PATH |
| | SHOWN TO ACCESS THE EAST STAIR. A MINIMUM OF TWO |
| | SEPARATE EXITS IS REQUIRED. |
| | |
| | 10. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL |
| | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS |
| | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND |
| | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA |
| | BUILDING CODE |
| | |
| | 11. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH |
| | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND |
| | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF |
| | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. |
| | |
| | 12. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE |
| | DOES NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL |
| | OPENINGS TO MEET THE DEFINITION OF AN OPEN PARKING |
| | GARAGE, IT WILL BE CONSIDERED AN ENCLOSED PARKING |
| | GARAGE AND MUST HAVE EXHAUST SYSTEMS. THE EXHAUST |
| | SYSTEMS SHALL BE DESIGNED TO MINIMIZE NOISE LEVELS |
| | USING INLINE FAN SILENCERS OR OTHER APPROVED METHODS. |
| | |
| | 13. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS |
| | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE |
| | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED |
| | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, |
| | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND |
| | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, |
| | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. |
| | |
| | 14. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC |
| | PLACES (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION |
| | OF PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, |
| | CONTACT SYBILLE WELTER, ART IN PUBLIC PLACES |
| | COORDINATOR, AT (561) 822-1521, OR BY EMAIL: |
| | [email protected] |
| | |
| | ROBERT BROWN |
| | BUILDING OFFICIAL |
| | TEL: 561 805 6652 |
| | EMAIL: [email protected] |
| | |
| |