| 2016-10-28 16:57:23 | REVIEW OF PLANS SUBMITTED 10/25/16: | | | 1. DEMOLITION PLAN SHEET DM-1 SHOWS THE REMOVAL OF 60 | | | LF OF EXFILTRATION TRENCH BUT ONLY 54 LF IS SHOWN TO BE | | | CONSTRUCTED ON SHEET PD-2. | | | | | | 2. HOW WILL EXFILTRATION TRENCH BE SURCHARGED? PROVIDE | | | A DETAIL FOR THE CONTROL STRUCTURE FOR THE EXFILTRATION | | | TRENCH. | | | | | | 3. SUGGEST ADDING STRUCTURES ON THE STORM PIPE BEING | | | DEFLECTED AROUND THE CLUBHOUSE EXPANSION. THESE WILL | | | PROVIDE MAINTENANCE ACCESS TO THE STORM PIPE. | | | | | | 4. HOW WILL NEW EXFILTRATION TRENCH PIPE CONNECT TO THE | | | EXISTING DRAINAGE PIPE? COULD THE EXFILTRATION SYSTEM | | | CONNECT DIRECTLY INTO EX-S12? | | | | | | 5. LEADER ARROW FOR "STORM PIPE" LABEL ON LANDSCPAE | | | PLAN LP-1.02 APPEARS TO POINT TO WALL INSTEAD OF THE | | | PIPE LINE. | | | | | | 6. DRAINAGE PERMIT MAY BE REQUIRED FROM THE NOTHERN | | | PALM BEACH COUNTY IMPROVEMENT DISTRICT. | | | | | | TRACY L. WARD, P.E. | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 | | | | | | |
| |