2016-08-09 23:15:30FROM: LAURA LE, PUBLIC UTILITIES ENGINEER
 AUGUST 9, 2016
  
 THIS IS A CONCEPTUAL LEVEL REVIEW.THE FOLLOWING MUST BE
 ADDRESSED PRIOR TO ISSUANCE OF CONSTRUCTION
 AUTHORIZATION INCLUDING BUILDING
 PERMITS AND ENGINEERING DEVELOPMENTAL APPROVAL:
  
 1. ADD EXISTING UTILITIES ON 41TH STREET AND
 N.FLAGLER/POINSETTIA STREET. LABEL PIPE INFORMATION -
 TYPE, MATERIAL, AND SIZE FOR PIPES AND SERVICES.
 2. CITY'S RECORD INFORMATION INDICATES EXISTING
 UTILITIES ON 41ST STREET INCLUDE A 6-INCH WATER MAIN,
 8-INCH SANITARY SEWER, AND 72-INCH STORMWATER PIPE
 3. CITY'S RECORD INFORMATION INDICATES EXISTING
 UTILITIES ON N FLAGLER/POINSETTIA STREET INCLUDE AN
 8-INCH WATER MAIN, 24-INCH SANITARY SEWER, AND 36-INCH
 STORMWATER PIPE
 4. EXISTING UTILITY SERVICE LINES, IF NOT USED BY THE
 SITE REDEVELOPMENT, ARE TO BE CUT AND CAPPED AT THE
 MAIN AND REMOVED (IF LARGER THAN 2 INCHES IN DIAMETER).
 RESTORE THE TRENCH CUT PER THE CITY'S STANDARD DETAILS