| 2017-07-06 16:50:32 | 2ND REVIEW |
| | |
| | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, |
| | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM |
| | BEACH FIRE RESCUE. |
| | |
| | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE |
| | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. |
| | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS |
| | ARE SUBMITTED FOR PERMIT. |
| | |
| | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE |
| | PROPOSED PROJECT. |
| | |
| | |
| | 1) FIRE PREVENTION'S PREVIOUS COMMENTS HAVE BEEN |
| | ADDRESSED. |
| | |
| | |
| | 2) THERE IS A CONCERN REGARDING THE FIRE PROTECTION IN |
| | THE PARKING GARAGE BASEMENT AREA. FIRE SPRINKLER |
| | PROTECTION IS REQUIRED IN THE BASEMENT AREA PER FLORIDA |
| | FIRE PREVENTION CODE, NFPA 1 |
| | |
| | 13.3.2.2 BASEMENTS EXCEEDING 2500 FT2 (232 M2) IN NEW |
| | BUILDINGS SHALL BE PROTECTED THROUGHOUT BY AN APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | PLEASE REIVEW AND ADDRESS FOR PLAN REVIEW SUBMITTAL |
| | PURPOSES. |
| | |
| | |
| | 3) THERE IS AN INDICATION THAT THE NEW PARKING GARAGE |
| | WILL BE OPEN; HOWEVER, PER THE FLORIDA FIRE PREVENTION |
| | CODE, NFPA 1 |
| | |
| | 13.3.2.4 NEW BUILDINGS THREE OR MORE STORIES IN HEIGHT |
| | ABOVE GRADE SHALL BE PROTECTED THROUGHOUT BY AN |
| | APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 13.3 UNLESS OTHERWISE PERMITTED BY 13.3.2.5. |
| | |
| | 13.3.2.5 STAND-ALONE OPEN PARKING STRUCTURES THAT ARE |
| | DETACHED FROM OTHER OCCUPANCIES SHALL NOT BE REQUIRED |
| | TO BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | THERE IS INSUFFICIENT DETAIL INDICATING THAT THE |
| | PROPOSED PARKING GARAGE IS DETACHED. |
| | |
| | PLEASE REIVEW AND ADDRESS FOR PLAN REVIEW SUBMITTAL |
| | PURPOSES. |
| | |
| | |
| | |
| | 4) THERE ARE INDICATIONS OF VALET DROPS |
| | OFFS/PORTE-COCHERES THAT DO NOT SHOW FIRE PROTECTION. |
| | PER THE FLORIDA FIRE PREVENTION CODE, NFPA 1 |
| | |
| | |
| | 13.3.2.6* EXTERIOR ROOFS, CANOPIES, PORTE-COCHERES, |
| | BALCONIES, DECKS, OR SIMILAR PROJECTIONS. IN BUILDINGS |
| | PROTECTED THROUGHOUT BY AUTOMATIC SPRINKLERS IN |
| | ACCORDANCE WITH NFPA 13, AUTOMATIC SPRINKLER PROTECTION |
| | SHALL BE PROVIDED FOR THE EXTERIOR SPACES IN ACCORDANCE |
| | WITH 13.3.2.6. |
| | |
| | PLEASE REIVEW AND ADDRESS FOR PLAN REVIEW SUBMITTAL |
| | PURPOSES. |
| | |
| | |
| | 5) THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES |
| | NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. |
| | |
| | |
| | 6) THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS |
| | AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| |