2018-01-26 14:32:27THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 12/19/17 REVIEW SUBMITTAL:
  
 1. THE TREE ROOT DETAIL IN THE LANDSCAPE PLANS MAKE
 REFERENCE TO PBCWUD UTILITIES. ADD A REFERENCE TO CWPB
 UTILTIES (WATER, SEWER, STORM). [REPEAT COMMENT].
  
 2. SHOW ROOT BARRIER ON THE LANDSCAPE PLANS FOR THE
 STORM PIPE BETWEEN THE EXISTING CB (BEING CONVERTED TO
 MH COVER) AND STRUCTURE S-105.
  
 3. THE ENGINEERING PLAN DOES NOT MATCH THE SITE PLAN
 AND LANDSCAPE PLANS. THE ENGINEERING PLAN DOES NOT SHOW
 THE LANDSCAPE ISLAND ON THE SOUTHWEST SIDE OF THE
 HANDICAP PARKING SPACES.
  
 4. DRAINAGE STRUCTURE S-101 IS TO HAVE TWO PRBS BECAUSE
 IT IS CONNECTED TO TWO EXFILTRATION TRENCHES. VERIFY
 THE PRBS WILL FIT IN A TYPE 'C' DITCH BOTTOM INLET.
  
 5. VERIFY THE EXISTING CB NORTH OF STRUCTURE S-101 WILL
 HAVE A TWO FOOT SUMP IN ORDER FOR A PRB TO BE INSTALLED
 ON THE SOUTH WALL.
  
 6. EXTEND THE SIDEWALK WITH CURB RAMPS TO THE EDGE OF
 PAVEMENT ON EACH SIDE OF BOYD STREET.
  